E-clipse bypass configurations (bcr, bdr, vcr, or vdr) for drives (1...400 hp)
Hide thumbs Also See for ACH550 series:
Table of Contents

Advertisement

E-Clipse Bypass Configurations for ACH550 Drives
Group 30
Code
Name
3001
UL ACTION
3002
UL TIME
3003
UL TRIP %
3004
COMM LOSS
3005
COMM TIME
3006
PHASE
LOSS
3007
PHASE SEQ
Group 32
Code
Name
3201
SUPER
CTRL
3202
START LVL
3203
STOP LEVEL
3204
START DLY
3205
STOP DLY
Resolution
Range
1
0 = NOT SEL
1 = FAULT
2 = WARNING
1 sec
10 - 400 sec
1%
0 - 100%
1
0 = NOT SEL
1 = FAULT
2 = CONST SP7
3 = LAST SPEED
0.1s
0.0 - 600.0s
1
0 = DISABLE
1 = ENABLE
1
0 = DISABLE
1 = ENABLE
Resolution
Range
1
0 = DISABLE
1 = ENABLE
1%
0 - 100%
1%
0 - 100%
1s
20 - 3600s
1s
20 - 3600s
Default
Description
NOT SEL
Selects action to be taken if
( 0)
underload occurs.
20 sec
Time below underload level
before fault is declared.
20%
Sets power level at which
underload is declared.
NOT SEL
This parameter serves similar
(0)
purpose as parameter 3018 in
drive which specifies behavior if
Modbus link goes down.
Difference is that this parameter
applies in drive and bypass
modes and if drive node or
bypass node detects a problem.
10.0s
Sets the communication fault
time used with COMM LOSS
parameter.
1
Disable for input phase loss.
1
Disable for input phase
sequence fault.
Default
Description
DISABLE
Enable supervisory control in
( 0)
bypass mode.
70%
Value of drive's AI2 that causes
bypass contactor closure.
Applies only in supervisory
mode.
30%
Value of drive's AI2 that causes
bypass contactor opening.
Applies only in supervisory
mode.
40s
Time that close condition must
be present before contactor is
closed.
Applies only in supervisory
mode.
60s
Time that open condition must be
present before contactor is
opened.
Applies only in supervisory
mode.
Parameter Descriptions
61