ABB ACH550 series User Manual page 84

E-clipse bypass configurations (bcr, bdr, vcr, or vdr) for drives (1...400 hp)
Hide thumbs Also See for ACH550 series:
Table of Contents

Advertisement

82
Alarm
Alarm Name In Panel
Code
4016
INP VOLTAGE LOW
4019
OVERRIDE 1
4020
OVERRIDE 2
4021
Selected by PAR 1621
START ENABLE 1
VIBRATION SWITCH
FIRESTAT
FREEZESTAT
OVERPRESSURE
VIBRATION TRIP
SMOKE ALARM
SAFETY OPEN
LOW SUCTION PRES
4022
Selected by PAR 1622
START ENABLE 2
VIBRATION SWITCH
LOW SUCTION PRES
4023
Selected by PAR 1623
START ENABLE 3
VIBRATION SWITCH
LOW SUCTION PRES
4024
Selected by PAR 1624
START ENABLE 4
VIBRATION SWITCH
LOW SUCTION PRES
Diagnostics and Troubleshooting
3-Phase input voltage
has not reached a
sufficient level to
enable editing of
parameters via the
keypad. This message
is generated within a
few seconds of power
up
Alarm is generated
when Smoke Control is
active
Alarm is generated
when Fireman's
Override is active
Alarm will occur when
start order is given and
the "RUN Enable" is
not present
Alarm will occur when
start order is given and
the "RUN Enable" is
not present
...
Alarm will occur when
start order is given and
the "RUN Enable" is
not present
...
Alarm will occur when
start order is given and
the "RUN Enable" is
not present
...
E-Clipse Bypass Configurations for ACH550 Drives
Alarm
Possible Cause
NA
NA
NA
Run Enable condition
is not satisfied.
Bad 24v supply
Bad digital input
24 V common is not
tied to Digital input
common on bypass
when using external 24
v supply
Run Enable condition
is not satisfied.
Bad 24v supply
Bad digital input
24 V common is not
tied to Digital input
common on bypass
when using external 24
v supply
Run Enable condition
is not satisfied.
Bad 24v supply
Bad digital input
24 V common is not
tied to Digital input
common on bypass
when using external 24
v supply
Run Enable condition
is not satisfied.
Bad 24v supply
Bad digital input
24 V common is not
tied to Digital input
common on bypass
when using external 24
v supply
Corrective Action
Loose J7 connector
Low input voltage.
Incoming voltage has
not reached at least
155 VAC within a few
seconds of powerup
Check Parameter
0103 and 0104 for
digital input status
Check Parameter
0103 and 0104 for
digital input status
Check 24 Volts on
RBCU unit
Check for 24 volts on
respective DI when
condition is satisfied
Check Parameter 0103
For status of digital
input
Check 24 Volts on
RBCU unit
Check for 24 volts on
respective DI when
condition is satisfied
Check Parameter 0103
For status of digital
input
Check 24 Volts on
RBCU unit
Check for 24 volts on
respective DI when
condition is satisfied
Check Parameter 0103
For status of digital
input
Check 24 Volts on
RBCU unit
Check for 24 volts on
respective DI when
condition is satisfied
Check Parameter 0103
For status of digital
input