ABB ACH550 series User Manual page 23

E-clipse bypass configurations (bcr, bdr, vcr, or vdr) for drives (1...400 hp)
Hide thumbs Also See for ACH550 series:
Table of Contents

Advertisement

E-Clipse Bypass Configurations for ACH550 Drives
that closed contacts or jumpers connect terminal X2:3 to X2:4 and X2:2 to X2:7 on
the bypass control board.
4. The Drive Selected LED should be illuminated. If not, press the Drive Select key to
switch to Drive mode. Leave the system in the Drive mode when proceeding to the
next step.
5. Press the Hand key on the ACH550 Control Panel. Press and hold the UP key until
the motor just starts rotating.
Note! If the ACH550 Control Panel displays an OVERCURRENT or EARTH FAULT,
disconnect and lock out power to the E-Clipse Bypass unit. Wait at least 5 minutes.
Disconnect the motor leads from the E-Clipse Bypass unit and Megger each motor
lead to ground to determine if the motor is good. Check the power leads from the
Drive / Bypass to the motor for damaged or improper wiring. If the ACH550 Control
Panel displays any other drive faults, correct the fault condition before proceeding to
the next step.
CAUTION: Check motor rotation direction as soon as the motor begins to
move. If motor does not rotate in the correct direction, shut down the drive,
disconnect and lock out power to the drive and wait five minutes. Swap any
two motor output wires (T1, T2, and T3). Incorrect motor rotation direction may
cause equipment damage.
6. Increase the speed to 60 Hz or the highest safe operating speed.
7. Press the OFF key on the drive control panel. The motor should stop.
CAUTION: Check the motor rotation direction in bypass.
Press the OFF/RESET key and then the Bypass Select key on the bypass
control panel. The Bypass Selected LED should illuminate solid green. Press
the Hand key and then quickly press the OFF key to "bump" the motor. If the
motor turns in the wrong direction, tag out/lock out, then swap any two input
power leads at the disconnect switch. Do not swap the motor leads.
If the drive does not operate according to these steps, refer to the ACH550-UH
User's Manual.
If the drive operates according to these steps, your ACH550 with E-Clipse Bypass is
ready to use with preset or modified macro settings.