E-Clipse Bypass Configurations for ACH550 Drives
Fault
Fault Name In Panel
Code
3013
DRIVE 1ST START
3014
COIL POW SUPPLY
3016
EARTH FAULT
3017
MTR UNDERLOAD
3018
MAX CYCLE FAULT
3019
DRIVE LINK FAULT
Fault
Fault generated if
attempting to close the
bypass contactor with
out running the bypass
in drive mode first.
Coil power supply has
failed to reach rated
voltage
Declared if attempting
to close the bypass
contactor when the
drive has earth fault
declared
If motor power(%) level
falls below minimum
power level establish in
parameter 30.03 for the
time (s) set in
parameter 30.02 fault
will be generated.
Parameter 30.03 is a
percentage of motor
power as defined in the
drive via parameter
99.09. Fault only
applies to bypass mode
Supervisory Mode only.
Declared if bypass
contactor is closed by
supervisory control 16
times within a 1 hour
period.
Supervisory Mode Only.
Fault generated if RS-
485 link between drive
and bypass stops
communicating.
Possible Cause
NA
Internal failure on
RBCU unit
Shorted contactor coil
Earth fault in motor
Broken belt
High and low levels of
hysteresis band are too
tight
Bad cable between
drive and bypass
Communication
improperly set in drive
Parameter
98.02(Modbus)
Application Macro in
99.02 set to 15 (text)
Check ACH550 E-clipse
user manual.
Diagnostics and Troubleshooting
75
Corrective Action
Run bypass unit in drive
mode before attempting
bypass mode
Cycle power on bypass
unit. If contactor coil is
shorted, fault 3023 or
3024 will be generated.
If 3023 or 3024 is
generated, replace
respective contactor
If 3023 or 3024 is not
generated on power up,
replace RBCU unit.
Refer to the ACH550
manual
Check load
Reset bypass keypad
Check ACH550 manual,
fault code 17, for further
action
Check parameters
32.02-32.05. Increase
time delays on
parameters 32.04 and
32.05
Proper seating of cable
in drive and
RBCU(connector J3)
Check drive parameter
98.02 and 99.02
Check drive Group 53
Follow DriveLink
recovery procedure