Vent Configurations - Lopi Radiant Plus GSB2 Small Installation Manual

Small inbuilt
Hide thumbs Also See for Radiant Plus GSB2 Small:
Table of Contents

Advertisement

18

Vent Configurations

Inlet & Exhaust Re-Line
Exhaust
Factory Built (Metal) Wood-
Burning Fireplace
NOTE: You may use either re-line configuration with a masonry or zero-clearance fireplace.
CAUTION: The "Exhaust Only Re-line" is not covered under the appliance safety standard (ANSI
) used in the safety certification of this appliance. The safety certification does not apply to this installation.
2.33
Before installing the appliance using this method, contact the Authority Having Jurisdiction to determine if this
installation is acceptable in your area. This type of installation requires a minimum chimney cross section of 48
square inches.
© Travis Industries
Installation (for qualified installers only)
Direct Vent Cap
(either high wind or Prairie)
6-5/8" to 3" & 3" Colinear
Adapter & Flashing
Inlet
Recommended Block-Off
Plate (must be non-
combustible - metal /
insulation). Prevents odors
from chimney entering
room.
Exhaust Only Re-Line
Masonry Fireplace
5/2/18-1476
Exhaust
Any cracks or
damage inside the
chimney must be
repaired.
A block-off plate must
seal the intake to the
chimney space. This
way air is drawn down
the chimney for
combustion air.
Block-Off Plate
(must be non-combustible -
metal / insulation)
Z21.88 CSA
Radiant Small GSB2