Troubleshooting
5.2.8 When Performing General-purpose Serial Communication
Error code
**0000
BCC error
**0001
Format error
**0002
NOT support error
**0003
Address error
Receive buffer
**0004
Overflow
**0005
Requested overflow
**0006
Data error
**0007
Data write inhibit error
5-12
Error name
The value of BCC may be incorrect. Check if there is no
calculation mistake.
A command format may be incorrect. Check if it is correct.
A command used is not supported with the version of the GT.
Upgrade the version of the GT, or use another command.
The address specified does not exist in the GT. Check the
address of the sent command.
The sent command exceeds the receivable number of bytes.
Check the number of bytes of the sent command.
The sent readout command exceeds the number of bytes that can
send back. Check the number of the read words.
The communication condition for the GT may be unmatched with
the condition for a destination device. Check the communication
conditions.
A command for the address that writing is not available was sent.
Check the address of the sent command.
Countermeasures