Description, device design, dimension drawing
2.2 Connections and terminal designation
Pin Terminal designation
1
BAT.
2
-
3
OK
4
ALARM
5
-
6
RDY TO BUFFER
7
BAT. > 85 %
8
-
9
ON/OFF
10
-
11
BAT. X2.1
12
BAT. X2.2
13
INTERRUPT
14
START
Relay contact: Contact rating, max. AC 30 V/0.5 A; DC 60 V/0.3 A; DC 30 V/1 A
The jumper (4a) (see Figure Signal connector (Page 21)) between pin 9 and 10 is necessary
to operate the device in buffer mode.
Delivery state: Jumper between pin 9 and 10
2.2.1.3
USB port
Figure 2-7
The USB interface (type B)
(see Section USB connector (Page 189)) is implemented using a defined cable/connector
(Y-Con USB - Yamaichi).
22
Function
24 V DC OK / BAT
REL1 (changeover contact):
Energized state: Normal operation
Quiescent state: Buffer mode or off
Ready for buffer operation / alarm
REL2 (changeover contact):
Energized state: Buffer mode is possible
Quiescent state: Not ready for buffering
Cycle 0.25 Hz: Defective battery
Battery > 85%
REL3 (NO contact):
Energized state: Buffering of the selected buffer time is possible,
or charge state > 85 %
On/Off (buffer operation permitted/prevented)
-
Battery communication or charging current setting
Battery supply or charging current setting
Interrupt (interruption of the output voltage)
Start from the battery
USB port
⑥
fully conforms to the USB 2.0 standard (12 MBd). Strain relief
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76