Connecting The Sitop Ups1600 At Its Input; Connecting The Sitop Ups1600 At Its Output - Siemens SITOP UPS1600 Manual

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

7.1

Connecting the SITOP UPS1600 at its input

SITOP UPS1600 is designed to be connected to a 24 V DC supply. The 24 V supply voltage
must be SELV in accordance with EN60950-1 and EN50178.
Figure 7-2
The 24 V power supply is connected at the "IN+", and "IN-"
side connection (Page 205)).
Cables must be used that are suitable for at least 90 °C (only for applications for UL508).
7.2

Connecting the SITOP UPS1600 at its output

The output of the SITOP UPS1600 is no-load, overload and short-circuit proof. If an overload
occurs, the electronic current limiting function limits the output current to a maximum value
(see Section Technical data (Page 211)).
Figure 7-3
The output voltage is connected at the "OUT+" and "OUT–"
side connection (Page 205)). Ensure that the output cables are dimensioned correctly for the
maximum output current rms value and fused accordingly.
The deployed cables must be suitable for temperatures of at least 90° C. (only for
applications for UL508)
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
Input side connection
Output-side connection
7.1 Connecting the SITOP UPS1600 at its input
terminals (see Figure Input
terminals (see Figure Output-
Installation
205

Hide quick links: