Preconditions
● The SITOP UPS1600 has been correctly connected and linked with the system.
● PG/PC with SITOP UPS Manager is connected with the system.
Procedure
1. Select "Display > Online functions".
2. Select "Update firmware".
3. To select the path to the directory with the unzipped files, click on the "Browse" button.
In this directory, select the "ups10a.upd", "ups20a.upd" or "ups40a.upd" file.
4. Click on the "Start" button.
The firmware is updated.
5. A message appears in the window area after the successful update.
6. Manually restart the SITOP UPS1600 by interrupting the SITOP UPS1600 power supply.
Restore the power supply to the SITOP UPS1600.
The firmware update has been performed successfully.
3.7

Web server

The web server is used to monitor the SITOP UPS1600. It operates independently of
UPS Manager and PROFINET access.
New functions of the web server from V2.1 and higher:
● Write access
● User administration
● Access via https
3.7.1

Accessing the web server

A Web browser is used for the access and operation.
The following Web browsers are suitable:
● Internet Explorer V8 (on MS Windows XP)
● Internet Explorer V10 (on MS Windows 7)
● Internet Explorer V11 (on MS Windows 7)
● Mozilla Firefox from V40 (on MS Windows 7)
● Google Chrome from V44 (on MS Windows 7)
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
Engineering and remote access
3.7 Web server
135