Engineering and remote access
3.7 Web server
Basic device configuration
"Buffering" parameters
Parameter
Connection threshold
Buffer time
Maximum buffer time
1)
Additional buffer time after PC shutdown.
Expected buffer current
1)
Reset time:
Enable reset after buffering
Parameter only available from SW version V2.0 and higher
1)
Parameter only available from SW version V2.1 and higher
2)
Valid from V2.0.4 or V2.1
3)
154
Value range
21 - 25 V
1 - 32767 s
Yes / No
1 - 300 s
3)
0 - 40 A
Yes / No
Initial value
22.5 V
600 s
No
60 s
0 A
5 s
No