Siemens SITOP UPS1600 Manual page 185

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Error
Ex-
Severity
Type
tended
Error
Type
257
17
F
257
18
F
257
20
MR
257
21
MR
257
22
MR
257
23
MR
257
24
F
257
26
MR
257
27
MR
258
1
F
258
2
F
258
3
MD
258
4
MD
258
5
F
258
6
MR
258
7
F
258
8
MD
258
9
MR
258
10
MR
258
11
MD
258
12
F
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
Alarm Text
UPS1600 parameters cor-
rupt
Device overtemperature
Low voltage mode
Buffering
Communication with device
failed
Device powered up
Wrong battery polarity
Insufficient charge level
Deep discharge battery
Battery defective (battery
index: {1:d})
Deep discharge battery, no
charging possible (battery
index: {1:d}).
Battery temperature high
(battery index: {1:d})
Battery temperature low
(battery index: {1:d}).
Communication with battery
fault (battery index: {1:d})
New battery detected (bat-
tery index: {1:d})
Wrong battery configuration
(battery index: {1:d})
Battery parameters corrupt
(battery index: {1:d}).
Battery replacement started
(battery index: {1:d})
Battery replacement fin-
ished (battery index: {1:d})
Battery replacement can-
celed (battery index: {1:d})
Fuse is defective (battery
index: {1:d})
Help Text
UPS1600-parameters corrupt - try to update the software.
Output and battery charging is switched off to prevent damage
to the device.
Input voltage of UPS1600 is too low. UPS1600 is not ready for
buffering.
Device is in the buffer mode.
PROFINET connection available - UPS1600 is defective
Device powered up
Wrong battery polarity - check battery connections.
Set buffer time can currently not be achieved due to low bat-
tery charge.
Battery is deep discharged - no buffering possible
Battery defective - check the fuse and the battery voltages
Battery is deep discharged - replace battery
Battery temperature too high - battery life will be shortened
Battery temperature too low - reduced output current
Communication with formerly known battery is no longer pos-
sible - check communication
A new battery was connected. The battery will be included in
the calculation of the total capacity and the charge parameters.
Different battery types connected. Only batteries of the same
type can be operated together.
Battery defective - replace battery
Remark:
Alarm is deactivated.
Battery replacement started by user
Battery replacement finished - counters have been reset
Battery replacement canceled - battery parameters are not
reset
Fuse is defective.
Troubleshooting
4.1 Hardware fault