Viessmann Vitotronic 200 KW2 Installation And Service Instructions Manual page 87

Weather-compensated, digital boiler and heating circuit control unit
Hide thumbs Also See for Vitotronic 200 KW2:
Table of Contents

Advertisement

Code 2
(cont.)
Coding in the delivered condition
DHW (cont.)
61 :
0
Cylinder primary pump will
be switched ON subject to
boiler temperature
62 : 10
Cylinder primary pump will
run on up to max. 10 min
64 :
2
During party mode:
Enable constant DHW
heating and DHW
circulation pump ON
66 :
4
Input of set DHW value:
at the programming unit
and the Vitotrol 300 control
unit (if installed)
67 : 40
With Vitosolic:
Third set DHW temperature
at 40 ºC. Reloading
at 40 C. Reloading
suppression will be active
above the selected
temperature. The DHW
cylinder is heated only by
solar heating system.
p
g
p g
g
Possible change
61 :
1
The cylinder primary pump
starts immediately
62 :
0
Cylinder primary pump
without run−on
62:
1
Max. run−on time
to
adjustable from 1 to 15 min
62 : 15
64 :
0
No DHW heating,
DHW circulation pump OFF
64 :
1
DHW heating and DHW
circulation pump according
to time program
66 :
0
At programming unit
66 :
1
At prrogramming unit and
remote control unit
Heating circuit A1
66 :
2
To programming unit and
remote control unit
Mixer circuit M2
66 :
5
At remote control unit
Heating circuit A1
66 :
6
At remote control unit
Mixer circuit M2
67 :
0
Without a third set DHW
temperature
67:
1
Input of a third set DHW
to
value; adjustable from 1 to
95 ºC (subject to the setting
67 : 95
of coding address 56)
Coding
87