Code 2
(cont.)
Coding in the delivered condition
Boiler circuit/mixer circuit
F2 :
0
No time limit for party
*1
mode
F8 :
5
For operation in reduced
room temperature mode,
the set room temperature
will be raised (up to the
temperature limit set by
coding address F9) to a
value subject to the outside
temperature, if the outside
temperature if the outside
temperature falls below
5 ºC.
Observe the setting of
coding address A3.
F9 : 14
Below an outside
temperature of 14 ºC, the
set room temperature will
be raised to the value
selected as set room
temperature, if the system
is in standard room
temperature mode
FA : 20
Raising the set flow
temperature for the
transition from reduced
temperature mode to
standard room
temperature mode by
about 20 %
Fb : 30
Duration for raising the set
flow temperature (see
coding address FA): 60 min
*1
Party mode ends automatically in the Heating and DHW program, when the system
changes over to operation with standard room temperature.
Possible change
F2 :
1
Time limit for party mode
to
adjustable from 1 to 12 h
F2 : 12
F8 : +10
Temperature limit for
to
cancelling reduced mode,
F8 : 60
adjustable from
+10 to 60 ºC
F8 : 61
Function disabled
F9 : +10
Limit for raising the set
to
room temperature to the
F9 : 60
value selected for standard
mode, adjustable from
+10 to 60 ºC
FA :
0
Raising the set flow
to
temperature for the
F9 : 50
transition from reduced
temperature mode to
standard room
temperature mode
adjustable from 0 to 50 %
Fb :
0
Duration for raising the set
to
flow temperature
Fb : 150
adjustable from 0 to
300 min;
1 setting step ¢ 2 min
Coding
*1
101