Viessmann Vitotronic 200 KW2 Installation And Service Instructions Manual page 90

Weather-compensated, digital boiler and heating circuit control unit
Hide thumbs Also See for Vitotronic 200 KW2:
Table of Contents

Advertisement

Coding
Code 2
(cont.)
Coding in the delivered condition
General (cont.)
86 :
5
Winter starts:
last week of month
87 :
7
Winter starts:
last day of the week
(Sunday)
88 :
0
Temperature displayed in
ºC (Celsius)
89 :
1
Automatic recognition of
KM BUS users
8A : 175
Do not adjust
8E :
4
Displaying and
acknowledging faults:
at the programming unit
and the remote control unit
(if installed)
90 : 128
Time constant for
calculating adjusted
outside temperature 21.3 h
90
p g
g
Possible change
86 :
1
Week 1
to
to
86 :
5
Week 5
87 :
1
Monday
to
to
87 :
7
Sunday
88 :
1
Temperature displayed in
ºF (Fahrenheit)
89 :
0
No user recognition
8E :
0
At programming unit
8E :
1
At programming unit and
remote control unit,
heating circuit A1
8E :
2
At programming unit and
remote control unit,
heating circuit M2
90 :
0
Fast (low values) or slow
to
(high values) matching of
90 : 199
flow temperature subject to
set value if the outside
temperature changes;
1 setting step ¢ 10 min

Advertisement

Table of Contents
loading

Table of Contents