Coding
Code 2
(cont.)
Coding in the delivered condition
Boiler/burner (cont.)
33 :
0
With control module V:
During external burner
demand, pumps and mixer
remain in control mode
General
54 :
0
Without solar control unit
DHW
55 :
0
Cylinder heating,
hysteresis $2.5 K
56 :
0
DHW temperature
adjustable from 10 to 60ºC
58 :
0
Without auxiliary function
for DHW heating
59 :
0
Cylinder heating:
Starting point
Switch−off point +2.5 K
60 : 20
During DHW heating, boiler
water temperature is max.
20 K higher than set DHW
temperature
86
Possible change
33 :
54 :
54 :
55 :
56 :
58:
to
58 : 95
59:
2.5 K
to
59 : 10
60 : 10
to
60 : 50
1
All pumps OFF ,
mixer closed
1
With Vitosolic 100;
will be recognised
automatically
2
With Vitosolic 200;
will be recognised
automatically
1
Adaptive cylinder heating
active
1
DHW temperature
adjustable from 10 to 95 ºC
Notes
H Observe the max.
permissible DHW
temperature.
H Change thermostat R
setting
1
Input of a second set DHW
value; adjustable
from 1 to 95 ºC (observe
coding address 56 and the
Auxiliary function section
on page 53)
1
Starting point adjustable
from 1 to 10 K below the
set value
The difference between the
boiler water temperature
and the set DHW
temperature is adjustable
from 10 to 50 K