Specification

Specification
Rated voltage:
230 V~
Rated
frequency:
50 Hz
Rated current:
6 A ~
Power
consumption:
5 W
Safety class:
I
Protection level: IP 20 D to EN 60 529;
safeguard through
appropriate design
and installation
Function:
Type 1 B to
EN 60 730 1
Permissible
ambient
temperature
H in operation: 0 to 40 ºC
Use in living space
and boiler rooms
(standard ambient
conditions)
H during storage
and transport: 20 to 65 ºC
110
Rated capacity of relay outputs at
230 V~ for
H Heating circuit
pumps sÖ:
H Cylinder storage
system sA:
H DHW circulation
pump sK:
H Mixer motor gS:
H Burner
plug fA:
Plug lÖ:
two−stage:
modulating:
H Total:
1
*
~
Total max. 4 A
*1
4 (2) A~
*1
4 (2) A~
*1
4 (2) A~
*1
0.2 (0.1) A~
4 (2) A~
1 (0.5) A~
0.1 (0.05) A~
max. 6 A~