Viessmann Vitotronic 200 KW2 Installation And Service Instructions Manual page 59

Weather-compensated, digital boiler and heating circuit control unit
Hide thumbs Also See for Vitotronic 200 KW2:
Table of Contents

Advertisement

Components from the parts list
Boiler temperature sensor and cylinder temperature sensor
760
740
720
700
680
660
640
620
600
580
560
540
0
20
0 40
Boiler water or
cylinder temperature in ºC
60
80 100 120 140
(cont.)
Connection
See page 16.
Checking sensor
1. Pull plug § or %.
2. Check the sensor resistance at
terminals 1 and 2 of the plug.
3. Compare the measurement with
the actual temperature (for
scanning, see page 31).
Check the installation and replace
sensor, if necessary, in case of
severe deviation.
Specification
Protection:
Permiss. ambient
temperature
H in operation
boiler
temperature
sensor:
cylinder
temperature
sensor:
H during storage
and transport:
Components
IP 32
0 to + 130 ºC
0 to + 190 ºC
20 to + 170 ºC
59