Settings and equipment
Settings and equipment
Function in the delivered condition
Heating circuit pumps
In the Heating and DHW program,
the heating circuit pumps are
switched OFF , when the outside
temperature exceeds the set room
temperature by more than 1 K.
In the DHW only program,
H the heating circuit pumps are
only started when there is a risk
of frost,
H any connected mixer stays closed
(when there is a risk of frost, it
changes to control mode).
Heating circuit 1 without mixer
Heating mode/reduced mode
weather−compensated
Heating circuit 2 with mixer
Heating mode/reduced mode
weather−compensated
112
(cont.)
Modified function
j Heating circuit pump for heating
circuit 1 remains ON
j Heating circuit pump for heating
circuit 2 remains ON
j Heating circuit pumps are switched
OFF before the set room
temperature is achieved
j Heating circuit pump for heating
circuit 1 or 2 are switched subject to
coding address b5
j Heating circuit pump for heating
circuit 2 is switched OFF , if the mixer
was closed longer than 12 min
j Heating mode: weather−compensated,
red. mode:
j Heating mode: with room temperature
red. mode:
j Heating mode/
red. mode:
j Heating mode: weather−compensated,
red. mode:
j Heating mode: with room
red. mode:
j Heating mode/
red. mode:
with room temperature
hook−up
hook−up,
weather−compensated
with room temperature
hook−up
with room
temperature hook−up
temperature hook−up,
weather−compensated
with room
temperature hook−up