Viessmann Vitotronic 200 KW2 Installation And Service Instructions Manual page 80

Weather-compensated, digital boiler and heating circuit control unit
Hide thumbs Also See for Vitotronic 200 KW2:
Table of Contents

Advertisement

Coding
Code 1
(cont.)
Summary
Coding in the delivered condition
System design
00 : 1
System version 1:
1 heating circuit without
mixer A1, without DHW
heating
Burner type
02 : 0
Single stage
Max. boiler temp.
06 : 85
Maximum limit of the
boiler water temperature
set to 85 ºC
DHW priority A1
A2 : 2
Cylinder priority to
y
heating circuit pump
80
g
p
y
Possible change
00 : 2
System version 1:
1 heating circuit without
mixer A1,
with DHW heating
00 : 3
System version 2:
1 mixer circuit M2, without
DHW heating
00 : 4
System version 2:
1 mixer circuit M2,
with DHW heating
00 : 5
System version 3:
1 heating circuit without
mixer A1 and 1 mixer
circuit M2, without DHW
heating
00 : 6
System version 3:
1 heating circuit without
mixer A1,
1 mixer circuit M2,
with DHW heating
02 : 1
Two−stage
02 : 2
Modulating
06 : 20
Maximum limit of the
to
boiler water temperature
06 : 130
adjustable from 20 to
130 ºC
A2 : 0
Without cylinder priority
A2 : 1
No function
A2 : 3
to
A2 : 15

Advertisement

Table of Contents
loading