How To Calibrate All Steer Sensors - Genie ZX-135/70 Service And Repair Manual

Hide thumbs Also See for ZX-135/70:
Table of Contents

Advertisement

Service and Repair Manual
Axle Components
How to C alibr ate All Steer Sensors
How to Calibrate All Steer
Sensors
Note: This procedure will only need to be
performed if the ground controls circuit board
(TCON) has been replaced.
Note: Perform this procedure with the axles
retracted and the tires straightened.
Note: Use the following chart to identify the
description of each LCD screen control button used
in this procedure.
Plus
Minus
1
Locate the calibration toggle switch at the top
of the ground control box. Activate calibration
mode by moving the toggle switch in the left
direction.
2
Temporarily install a control box door retaining
fastener between the door and the box to
prevent the control box door from moving the
toggle switch while calibrating the machine.
3
Turn the key switch to ground controls and pull
out the ground controls red Emergency Stop
button to the on position.
4
Loosen the steer angle sensor cover retaining
fasteners. Do not remove the fasteners or the
sensor cover.
5
Using a voltmeter set to DC voltage, probe the
back of the electrical connector at pins B and
C.
130
Previous
Enter
ZX®-135/70
6
Left front (square-end, blue side) and right
rear (circle-end, yellow side) angle
sensors: Rotate the sensor cover clockwise
or counterclockwise until the voltage reading
is between 1.4 to 1.6V DC. Tighten the sensor
cover fasteners.
Right front (square-end, yellow side) and
left rear (circle-end, blue side) angle
sensors: Rotate the sensor cover clockwise
or counterclockwise until the voltage reading
is between 3.4 to 3.6V DC. Tighten the sensor
cover fasteners.
Note: If available, WebGPI can also be used for
this procedure.
7
Remove the key from the main key switch.
Insert the key into the bypass/recovery key
switch and turn it to the bypass position.
Note: The angle sensor calibration values will not
be saved correctly unless the key switch is in the
bypass position and the calibration toggle switch is
activated.
8
Push in the red Emergency Stop button to the
off position.
April 2018