Alarm Output Function - Mitsubishi QD60P8-G User Manual

Melsec-q series, channel isolated pulse input module
Table of Contents

Advertisement

5 DETAILS AND SETTING OF FUNCTIONS

5.8 Alarm Output Function

Item
Alarm output selection
Alarm output setting value
upper/upper limit
Alarm output setting value
upper/lower limit
Alarm output setting value
lower/upper limit
Alarm output setting value
lower/lower limit
Item
Sampling pulse number
Alarm output flag
5 - 15
With "alarm output function valid" set in the "alarm output selection" of the
buffer memory, the alarm output function outputs an alarm if the "sampling
pulse number" of the buffer memory exceeds the upper/upper limit value or
lower/lower limit value. The alarm is turned OFF if the sampling pulse number
is below the upper/lower limit value or above the lower/upper limit value after
the output of the alarm.
To set the alarm output function, set four points: upper/upper limit value,
upper/lower limit value, lower/upper limit value and lower/lower limit value.
The buffer memory addresses related to the setting of the alarm output
function are as follows.
Setting value
0: Alarm output function
invalid
1: Alarm output function
valid
0 to 32767
If the setting value is other than in the above values or does not establish the following
relation expression, an alarm output setting range outside error (error code: 500)
occurs.
Upper/upper limit
upper/lower limit
To clear the error, turn ON the error reset request (Y8 to YF) of the corresponding
channel.
After this, set a correct value (value that will establish the above relation expression
and is within the setting range), and then turn ON the operating condition setting
request flag (Y1).
The buffer memory addresses related to the alarm output are as follows.
Read value
0 to 32767
bit0: Lower limit alarm
bit8: Upper limit alarm
[Bit pattern of alarm output]
b15
b8
Not used
Not used
CH1
CH2
17
49
19
51
20
52
21
53
22
54
lower/upper limit
CH1
CH2
0
32
18
50
b4
b0
Storage Item
Meaning
Lower limit alarm
0:OFF(Normal)
1:ON(Range over)
Upper limit alarm
Buffer memory address
CH3
CH4
CH5
CH6
81
113
145
177
83
115
147
179
84
116
148
180
85
117
149
181
86
118
150
182
lower/lower limit
Buffer memory address
CH3
CH4
CH5
CH6
64
96
128
160
82
114
146
178
MELSEC-Q
CH7
CH8
209
241
211
243
212
244
213
245
214
246
CH7
CH8
192
224
210
242
5 - 15

Advertisement

Table of Contents
loading