3.5 Interface with External Devices

Input/
Internal circuit
Output
Input
-
3 - 14
The internal circuit of the QD60P8-G interface for connection of external devices is
shown in a schematic diagram.
Terminal
number
1, 3, 5, 7,
9, 11,
13, 15
2, 4, 6, 8,
10, 12,
14, 16
17
-
18
*: Use the intelligent function module switch to change between 5VDC and 12 to 24VDC.
(For details, refer to "Section 4.5 Switch setting for intelligent function module".)
Signal layout of each channel
Terminal number
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
Signal name
Operation
5VDC *
CH1 to 8 V+
At ON
12 to 24VDC *
5VDC *
CH1 to 8 V-
At OFF
12 to 24VDC *
FG
-
Signal name
1
CH1 V+
2
CH1 V-
3
CH2 V+
4
CH2 V-
5
CH3 V+
6
CH3 V-
7
CH4 V+
8
CH4 V-
9
CH5 V+
10
CH5 V-
11
CH6 V+
12
CH6 V-
13
CH7 V+
14
CH7 V-
15
CH8 V+
16
CH8 V-
MELSEC-Q
Input voltage
Operating current
(guaranteed
(guaranteed
value)
value)
3.5V to 5.5V
4mA or more
10.2 to 30V
4mA or more
1.0V or less
0.5mA or less
2.0V or less
0.5mA or less
-
-