Transmitter in housing for field or top-hat rail mounting for the ultrasonic sensors endress+hauser fdu91; endress+hauser fdu91f; endress+hauser fdu92; endress+hauser fdu93; endress+hauser fdu95; endress+hauser fdu96 (36 pages)
Summary of Contents for Endress+Hauser Prosonic S FMU90
Page 1
Brief Operating Instructions Prosonic S FMU90 Level Measurement Alternating Pump Control Rake Control These Instructions are Brief Operating Instructions; they do not replace the Operating Instructions included in the scope of supply. For detailed information, refer to the Operating Instructions and other documentation on the CD-ROM provided or visit "www.endress.com/...
Safety Instructions Safety Instructions Designated use The Prosonic S FMU90 is a transmitter for the ultrasonic sensors FDU90, FDU91, FDU91F, FDU92, FDU93, FDU95 and FDU96. The sensors of the class FDU8x can be connected as well. Installation, commissioning, operation The Prosonic S is fail-safe and constructed to the state-of-the-art. It meets the appropriate standards and EC directives.
Mounting Prosonic S FMU90 Level Measurement HART Safety icons Safety conventions Warning! A warning highlights actions or procedures which, if not performed correctly, will lead to personal injury, a safety hazard or destruction of the instrument " Caution! Caution highlights actions or procedures which, if not performed correctly, may lead to personal injury or...
Prosonic S FMU90 Level Measurement HART Mounting Installation 2.2.1 Installation conditions of the field housing Weather protection In order to avoid excessive sunlight exposure, the instrument should be mounted in a position which is protected against direct sunlight or a protection cover should be applied.
Page 6
Mounting Prosonic S FMU90 Level Measurement HART 2.2.2 Installation conditions of the DIN-rail housing • The DIN-rail housing must be mounted outside hazardous areas in a cabinet. • The housing is mounted on a DIN rail EN 60715 TH 35 x 7.5 or TH 37 x 15.
Prosonic S FMU90 Level Measurement HART Mounting Mounting the remote display and operating module 2.3.1 Scope of delivery If the Prosonic S is ordered with the display for cabinet door mounting, the following is contained in the scope of delivery: •...
Page 8
Mounting Prosonic S FMU90 Level Measurement HART 2.3.3 Mounting L00-FMU90xxx-17-00-00-xx-002 Note! For more information and details, see the Operating Instructions BA00288F on the CD-ROM provided. 2.3.4 Adaption plate If an opening of 138 x 138 mm (5.43 x 5.43 in) and the remote display of the Prosonic FMU860/861/862 are already present, you can use the adaption plate (Order Code: 52027441).
Prosonic S FMU90 Level Measurement HART Mounting L00-FMU90xxx-06-00-00-xx-006 1 Remote display of the FMU90 with adaption plate 2 Remote display of the FMU860/861/862 Mounting of the sensors Information on the mounting of the sensors can be found in the following documents: •...
Wiring Prosonic S FMU90 Level Measurement HART Wiring Warning! The instrument may only be installed if the supply voltage is switched off. Terminal compartment of the field housing The field housing has a separate terminal compartment. It can be opened after loosening the four screws of the lid.
Prosonic S FMU90 Level Measurement HART Wiring 3.1.1 Cable entries of the field housing The following openings for cable entries are prestamped on the bottom of the housing: M20x1.5 (10 openings), M16x1.5 (5 openings), M25x1.5 (1 opening) The required number and types of cable entries depend on the application at hand.
Page 12
Wiring Prosonic S FMU90 Level Measurement HART 3.2.2 Several instruments mounted side by side L00-FMU90xxx-04-00-00-xx-012 Note! • The cables can be inserted into the housing from above or from below. • The pictures show the smallest housing version but are valid for the larger versions as well.
Prosonic S FMU90 Level Measurement HART Wiring Terminal assignment Pluggable spring-force terminals for connection of the cables are supplied in the terminal compartment. Rigid conductors or flexible conductors with cable sleeve can directly be inserted and are contacted automatically. Conductor cross section 0.2 mm...
Page 14
Wiring Prosonic S FMU90 Level Measurement HART Relay DigIn 0/4...20mA Sync Service Fuse Display FDU- Sensor HART 0/4…20mA FDU- FDU- Sensor Sensor Relay L00-FMU90xxx-04-00-00-xx-001 Terminals of the Prosonic S (the terminals depicted in grey are not present in every instrument version)
Page 15
Prosonic S FMU90 Level Measurement HART Wiring Terminals Meaning Terminal area Remarks Analog output 2 (optional); only for the version with two analog outputs; 41, 42 4 to 20 mA/ no HART signal at this output 0 to 20 mA...
Wiring Prosonic S FMU90 Level Measurement HART Warning! When using the public supply mains, an easily accesible power switch must be installed in the proximity of the device. The power switch must be marked as a disconnector for the device (IEC/EN 61010).
Prosonic S FMU90 Level Measurement HART Wiring Connection of the sensor heater (for FDU90/FDU91) The FDU90 and FDU91 sensors are available in a version with heater. For more information and details, see the Technical Information TI00396F on the CD-ROM provided.
Page 18
Wiring Prosonic S FMU90 Level Measurement HART 3.5.2 Connection in the DIN-rail housing The supply voltage must be provided in the cabinet, e.g. by a terminal on the DIN-rail: FMU90 Sync Service Fuse Display HART 0/4…20mA FDU- Sensor Relay FDU90...
The maximum short-circuit current at 24 V is 20 mA. Connection of a temperature sensor The Prosonic S FMU90 transmitter has an optional input for an external temperature probe (in the product structure: feature 90 "Additional input", option B). The following probes can be connected: •...
Page 20
Wiring Prosonic S FMU90 Level Measurement HART 3.7.1 FMT131 (Endress+Hauser), (connectable to FMU90-********B***) FMU90 FMU90 FMU90 YEGN YEGN YEGN FMT131-R FMT131-J FMT131-J L00-FMU90xxx-04-00-00-xx-019 A Non-Ex area (FMT131-R) black B Ex area (FMT131-J) with grounding in the FMU90 yellow C Ex area (FMT131-J) with grounding at a terminal box...
Prosonic S FMU90 Level Measurement HART Wiring Synchronization line • If wiring several Prosonic S (FMU90/FMU95) which are mounted in a common cabinet and if the sensor cables run in parallel, the FMU90 FMU90 FMU90 synchronization terminals (39 and 40) must be interconnected.
Wiring Prosonic S FMU90 Level Measurement HART Connection of the separate display and operating module Sync Service Fuse Display HART 0/4…20mA FDU- Sensor Relay L00-FMU90xxx-04-00-00-xx-005 1 Connection of the display plug with the cable (3 m (9.8 ft)) For the version of the Prosonic S with a separate display for panel mounting, a pre-assembled connecting cable (3 m (9.8 ft)) is supplied.
Page 23
Prosonic S FMU90 Level Measurement HART Wiring Example Sync Service Fuse Display HART 0/4…20mA FDU- Sensor Relay GNYE FDU91F/93/95/96 90 … 253 VAC (FDU83/84/85/86) 10,5 … 32 VDC L00-FMU90xxx-04-00-00-xx-007 1 The wire is already connected on delivery Endress+Hauser...
Page 24
Wiring Prosonic S FMU90 Level Measurement HART 3.10.2 Potential equalization for the DIN-rail hosuing If the DIN-rail housing is used, the potential equalization must be connected in the cabinet, e.g. at a metallic DIN rail: Sync Service Fuse Display HART 0/4…20mA...
Prosonic S FMU90 Level Measurement HART Wiring Note! The longest required distance has to be taken into account when removing the jacket of the sensor cable (GNYE in the above example). 3.11 Post-connection check After wiring the transmitter, carry out the following checks: •...
Operation Prosonic S FMU90 Level Measurement HART Operation Operating options • Via the operating and display module at the Prosonic S (if present) • Via the service interface of the Prosonic S with the Commubox FXA291 and the operating program "FieldCare"...
Page 27
Prosonic S FMU90 Level Measurement HART Operation Display symbols Symbol Meaning Operating mode of the instrument User User parameters can be edited. Service parameters are locked. Diagnosis The service interface is connected. Service User and service parameters can be edited.
Page 28
Operation Prosonic S FMU90 Level Measurement HART Keys (softkey operation) The function of the keys depends on the current position within the operating menu (softkey functionality). The key functions are indicated by softkey symbols in the bottom line of the display.
Page 29
Prosonic S FMU90 Level Measurement HART Operation General key combinations The following key combinations do not depend on the menu position: Key combination Meaning Escape • While editing a parameter: Exit the editing mode without accepting the changes. • Within the navigation: Move upwards to the previous layer of the menu.
Page 30
Operation Prosonic S FMU90 Level Measurement HART 4.2.2 The operating menu Structure of the menu The parameters of the Prosonic S are organized in an operating menu (consisting of a main menu and several submenus). Parameters which are related to each other are comprised in a common parameter set.
Prosonic S FMU90 Level Measurement HART Commissioning Commissioning Warning! For the version with field housing: The instrument may only be operated if the field housing is closed. First setup After switching on the power supply for the first time, the instrument asks for a number of operating parameters: •...
Commissioning Prosonic S FMU90 Level Measurement HART Basic setup After the first setup the main screen appears. However, the displayed value does not correspond to the real level before you have performed the basic setup. To do so, enter the main menu by pressing "Menu" (right key).
Page 33
Prosonic S FMU90 Level Measurement HART Commissioning Step Parameter set Parameter Remarks → unit level → unit level Select the unit for the level measurement. → level Displays the currently measured level. → distance Displays the currently measured distance between the reference point of the sensor and the product level.
Page 34
Commissioning Prosonic S FMU90 Level Measurement HART Step Parameter set Parameter Remarks → distance mapping → act. distance 1 Indicates the currently measured distance between (Details → Chap. 5.2.5) → act. distance 2 the reference point of the sensor and the product surface.
Prosonic S FMU90 Level Measurement HART Commissioning 5.2.2 Application parameters Parameter Selection/Remarks "tank shape" Use this parameter to specify the tank shape of your application: Selection: • dome ceiling (→ A) • horizontal cyl. (→ B) • bypass (→ C) •...
Page 36
Commissioning Prosonic S FMU90 Level Measurement HART "process conditions" for the following situations Example filter settings standard liquid for all fluid applications The filters and output damping are set which do not fit in any of the to average values.
Page 37
Prosonic S FMU90 Level Measurement HART Commissioning "process conditions" for the following situations Example filter settings solid dusty Dusty bulk solids The averaging filters are set to detect even relatively weak signals. conveyor belt Bulk solids with rapid level The averaging filters are set to small change values.
Page 38
Commissioning Prosonic S FMU90 Level Measurement HART 5.2.3 Empty and full calibration Parameter Remarks "empty calibration" Use this parameter to specify the empty distance E, i.e. the distance between the reference point of the sensor and the minimum level (zero point).
Page 39
Prosonic S FMU90 Level Measurement HART Commissioning 5.2.4 Linearization Parameter Selection/Remarks "type" Note! Number and type of the parameters in this set depend on the selected linearization type. Only the parameters "type" and "mode" are always present. Selection • none In this linearization type the measured level is not converted but displayed in the selected level unit (see "unit level").
Page 40
Commissioning Prosonic S FMU90 Level Measurement HART Parameter Selection/Remarks "type" In these linearization types the measured level is convertet to the volume in a horizontal cylinder or a spherical tank. Selection • horizontal cylinder • sphere The following additional parameters have to be specified: •...
Page 41
Prosonic S FMU90 Level Measurement HART Commissioning Parameter Selection/Remarks "type" In this linearization mode the measured value is calculated from a linearization table. The table may consist of up to 32 pairs of values (level - volume). The table must be monoto- nically increasing or decreasing.
Page 42
Commissioning Prosonic S FMU90 Level Measurement HART Parameter Selection/Remarks The table editor Level Level Value Value 0,0000 0,0000 0,0000 0,0000 0,0000 0,0000 0,0000 0,0000 0,0000 0,0000 0,0000 0,0000 … … 0,0000 0,0000 0,0000 0,0000 : go to next row : navigate within the table : go to previous row : (for "Level"...
Page 43
Prosonic S FMU90 Level Measurement HART Commissioning 5.2.5 Interference echo suppression: Basic principles Parameter Remarks "check value" The "check value" and "distance mapping" parameters are used to configure the "distance mapping" interference echo suppression of the Prosonic S. The following picture shows the operating principle of the interference echo suppression:...