Endress+Hauser Cerabar S PMP71 Brief Operating Instructions

Mid part certificate process pressure measurement
Hide thumbs Also See for Cerabar S PMP71:

Advertisement

KA01095P/00/EN/13.16
71336225
Products
Brief Operating Instructions
Cerabar S PMP71
with MID Part Certificate
Process pressure measurement
These Instructions are Brief Operating Instructions; they are not
a substitute for the Operating Instructions pertaining to the
device.
Detailed information about the device can be found in the
Operating Instructions and the other documentation:
Available for all device versions via:
– Internet:
www.endress.com/deviceviewer
– Smart phone/tablet: Endress+Hauser Operations App
Solutions
Services

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Cerabar S PMP71

  • Page 1 Operating Instructions pertaining to the device. Detailed information about the device can be found in the Operating Instructions and the other documentation: Available for all device versions via: – Internet: www.endress.com/deviceviewer – Smart phone/tablet: Endress+Hauser Operations App...
  • Page 2: Serial Number

    Cerabar S 4 to 20 mA HART Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
  • Page 3: Table Of Contents

    6.7 Endress+Hauser operating program ........
  • Page 4: Document Information

    A connection that has to be connected ground prior to establishing any other to the plant grounding system: This may connections. be a potential equalization line or a star grounding system depending on national or company codes of practice. Endress+Hauser...
  • Page 5 Indicates procedures, processes or actions that are forbidden. A0011184 Indicates additional information. A0011193 Reference to documentation A0028658 Reference to page A0028659 Reference to graphic A0028660 Series of steps 1. 2. 3. … A0031595 Result of a sequence of actions A0018343 Visual inspection A0028673 Endress+Hauser...
  • Page 6: Registered Trademarks

    Registered trademarks of E.I. Du Pont de Nemours & Co., Wilmington, USA TRI-CLAMP Registered trademark of Ladish & Co., Inc., Kenosha, USA HART Registered trademark of the HART Communication Foundation, Austin, USA. ® GORE-TEX Registered trademarks of W.L. Gore & Associates, Inc., USA Endress+Hauser...
  • Page 7: Terms And Abbreviations

    Also observe pressure-temperature dependency. For the relevant standards and additional notes, see technical information. The MWP may be applied for an unlimited time. Maximum sensor Range between LRL and URL measuring range This span is the maximum calibratable/adjustable measuring span. Endress+Hauser...
  • Page 8: Turn Down Calculation

    • Upper range value (URV) = 5 bar (75 psi) Turn down (TD): |URV LRV| 10 bar (150 psi) |5 bar (75 psi) 0 bar (0 psi)| In this example, the TD is thus 2:1. This span is based on the zero point. Endress+Hauser...
  • Page 9: Basic Safety Instructions

    The manufacturer is not liable for damage caused by improper or non-designated use. Verification for borderline cases: For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability.
  • Page 10: Hazardous Area

    Identification Cerabar S 4 to 20 mA HART dangers: ‣ If, despite this, modifications are required, consult with Endress+Hauser. Repair To ensure continued operational safety and reliability, ‣ Carry out repairs on the device only if they are expressly permitted.
  • Page 11: Device Designation

    Scope of delivery The scope of delivery comprises: • Cerabar S pressure transmitter • For devices with the "HistoROM/M-DAT" option: CD-ROM with Endress+Hauser operating program • Optional accessories Documentation supplied: • Operating Instructions BA00412P and BA00413P are available via the Internet.
  • Page 12: Certificates And Approvals

    The device complies with the applicable standards and regulations as listed in the EC Declaration of Conformity and thus complies with the statutory requirements of the EC Directives. Endress+Hauser confirms the successful testing of the device by affixing to it the CE mark.
  • Page 13: General Installation Instructions

    • To ensure optimal readability of the onsite display, it is possible to rotate the housing up to 380°.  ä 16, "Rotating the housing". • Endress+Hauser offers a mounting bracket for installing on pipes or walls.  ä 16, "Wall and pipe mounting (optional)".
  • Page 14 The orientation depends on the measuring application. • Do not clean or touch process isolating diaphragms with hard or pointed objects. • To comply with ASME-BPE requirements regarding cleanability (Part SD Cleanability), the device must be installed as follows: Endress+Hauser...
  • Page 15 Corrupted measurement results. The seal is not allowed to press against the process isolating diaphragm as this could affect the measurement result. ‣ Ensure that the seal is not touching the process isolating diaphragm. A0017743 Fig. 2: Process isolating diaphragm Seal Endress+Hauser...
  • Page 16 When closing the housing cover, please ensure that the thread of the cover and housing are free from dirt, e.g. sand.If you feel any resistance when closing the cover, check the thread on both again to ensure that they are free from dirt. Endress+Hauser...
  • Page 17: Post-Installation Check

    • When using the measuring device in hazardous areas, installation must comply with the corresponding national standards and regulations and the Safety Instructions or Installation or Control Drawings. • Devices with integrated overvoltage protection must be grounded. • Protective circuits against reverse polarity, HF influences and overvoltage peaks are integrated. Endress+Hauser...
  • Page 18 Minimum supply voltage = 10.5 V DC, jumper is inserted in accordance with the illustration. Minimum supply voltage = 11.5 V DC, jumper is inserted in "Test" position. Devices with integrated overvoltage protection are labeled OVP (overvoltage protection) here. Endress+Hauser...
  • Page 19 5.1.2 Connecting devices with an M12 connector PIN assignment for M12 connector Meaning Signal + Not assigned Signal – Earth A0011175 5.1.3 Connecting the cable version – gnye 4...20 mA P01-PMx4xxxx-04-xx-xx-xx-010 Fig. 6: rd = red, bk = black, gnye = green-yellow Endress+Hauser...
  • Page 20: Connecting The Measuring Unit

    (Thus, the output current can be measured without interruption via the diode.) – Order configuration – Minimum supply voltage: 11.5 V DC – Taking 4 to 20 mA test signal via plus and test terminal: not possible. Test Test – Minimum supply voltage: 10.5 V DC Endress+Hauser...
  • Page 21 • External ground terminal: 0.5 to 4 mm (20 to 12 AWG) 5.2.3 Cable specification • Endress+Hauser recommends using twisted, shielded two-wire cables. • Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in) 5.2.4 Load U – 10.5 V U –...
  • Page 22: Potential Equalization

    • Are all the screws firmly tightened? • Are the housing covers screwed down tight? As soon as voltage is applied to the device, the green LED on the electronic insert lights up for a few seconds or the connected onsite display lights up. Endress+Hauser...
  • Page 23: Operation

    • Option for configuring the display according to individual requirements, such as language, alternating display, contrast setting, display of other measured values such as sensor temperature • Comprehensive diagnostic functions (fault and warning message, maximum indicators, etc.) • Rapid and safe commissioning with the Quick Setup menus Endress+Hauser...
  • Page 24 Cerabar S 4 to 20 mA HART Parameter Measured value display Identification Function name Value number Header line Main line Unit Information line Symbol – Bargraph Bargraph Editing modes Operating keys Selection options Value that can be edited Current measured value P01-xMx7xxxx-07-xx-xx-xx-001 Endress+Hauser...
  • Page 25: Operating Elements

    In hygienic stainless steel housings (T17), the operating keys are always located inside on the electronic insert. Operating keys are also integrated on the optional onsite display. Endress+Hauser...
  • Page 26 For a detailed description, also see  ä 28, "Pressure measuring mode". Position adjustment. Reset all parameters. The reset via operating keys corresponds to the software reset code 7864. ® Copy the configuration data from the optional HistoROM /M-DAT module to the device. Endress+Hauser...
  • Page 27: Onsite Operation

    The terms function group, level and selection level are explained in  ä 29, "General structure of the operating menu". Onsite operation – onsite display not connected ® To operate the device with a HistoROM /M-DAT module, see Page  ä 32, "HistoROM®/M-DAT (optional)". Endress+Hauser...
  • Page 28 Observe the input Observe the input Observe the input limits. limits. limits. Please note warning on Page  ä 33, "Commissioning". Endress+Hauser...
  • Page 29: Onsite Operation

    OPERATING MENU LANGUAGE MEASURING MODE ➀ ➁ SETTINGS DISPLAY POSITION ADJUSTMENT BASIC SETUP EXTENDED SETUP ➂ POS. INPUT VALUE ➃ CALIB. OFFSET P01-MIDxxxxx-19-xx-xx-en-029 Fig. 10: General structure of the operating menu 1. Selection level 2. Selection level Function groups Parameters Endress+Hauser...
  • Page 30  ä 27, "Function of the operating elements – onsite display connected". Onsite display Operation The onsite display shows the parameter to be changed. The value highlighted in black can be changed. The "s" unit is fixed and cannot be changed. P01-xxxxxxxx-19-xx-xx-xx-023 Endress+Hauser...
  • Page 31 – Jump to the next parameter with "E" . – You can get back to the editing mode with "+" or "–". P01-xxxxxxxx-19-xx-xx-xx-032 6.4.4 Taking pressure applied at device as value Example: configuring upper-range value – assigning 20 mA to the pressure value 400 mbar (6 psi). Endress+Hauser...
  • Page 32: HistoromĀ®/M-Dat (Optional)

    URV (see next graphic). P01-xxxxxxxx-19-xx-xx-xx-037 Switch to the next parameter with "E" . P01-xxxxxxxx-19-xx-xx-xx-035 ® HistoROM /M-DAT (optional) See operating instructions. Operation via HART handheld terminal See operating instructions. Endress+Hauser operating program See operating instructions. Locking/unlocking operation See operating instructions. Endress+Hauser...
  • Page 33: Factory Setting (Reset)

    Function check Carry out a post-installation and a post-connection check as per the checklist before commissioning the device. • "Post-installation check" checklist  ä 17. • "Post-connection check" checklist  ä 22 Endress+Hauser...
  • Page 34: Selecting Language And Measuring Mode

    Due to the orientation of the device, there may be a shift in the measured value, i.e. when the container is empty or partially filled, the measured value does not display zero. There are three options to choose from when performing position adjustment. (Menu path: (GROUP SELECTION ) OPERATING MENU SETTINGS POSITION ADJUSTMENT) Endress+Hauser...
  • Page 35: Pressure Measurement

    "Description of device functions" – Table 6, POSITION ADJUSTMENT – Table 7, BASIC SETUP – Table 15, EXTENDED SETUP • For differential pressure measurement, select the "Pressure" option by means of the MEASURING MODE parameter. The operating menu is structured accordingly. Endress+Hauser...
  • Page 36 Measured value display Switch from the measured value display to GROUP Select QUICK SETUP menu. SELECTION with F. GROUP SELECTION MEASURING MODE Select MEASURING MODE parameter. Select "Pressure" option. MEASURING MODE Select "Pressure" option. GROUP SELECTION Select QUICK SETUP menu. Endress+Hauser...
  • Page 37: Lead Sealing Plan

     ä 27, "Function of the operating elements – onsite display connected" and  ä 29, "Onsite operation – onsite display connected". Lead sealing plan Lead sealing of the housing cover is provided for use in applications subject to custody transfer regulations: Endress+Hauser...
  • Page 38 Commissioning Cerabar S 4 to 20 mA HART P01-MIDxxxxx-19-xx-xx-xx-031 Endress+Hauser...
  • Page 39 Cerabar S 4 to 20 mA HART Commissioning Endress+Hauser...
  • Page 40 71336225 www.addresses.endress.com...

Table of Contents