Endress+Hauser Cerabar S PMP71 Operating Instructions Manual

Endress+Hauser Cerabar S PMP71 Operating Instructions Manual

With mid part certificate process pressure measurement
Hide thumbs Also See for Cerabar S PMP71:

Advertisement

Operating Instructions

Cerabar S PMP71 with MID Part Certificate
Process pressure measurement
BA00412P/00/EN/02.12
71185804
Valid for software version:
02.10.54

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Cerabar S PMP71

  • Page 1: Operating Instructions

    Operating Instructions Cerabar S PMP71 with MID Part Certificate Process pressure measurement BA00412P/00/EN/02.12 71185804 Valid for software version: 02.10.54...
  • Page 2 Overview of documentation Cerabar S PMP71 with 4 to 20 mA HART Overview of documentation Device Documentation Content Remarks Cerabar S Technical Information TI00383P Technical data 4 to 20 mA HART Operating Instructions BA00412P – Identification – Installation – Wiring –...
  • Page 3: Table Of Contents

    Operation via HART handheld terminal ..31 Endress+Hauser operating program ... . 31 Locking/unlocking operation ....31 Factory setting (reset) .
  • Page 4: Safety Instructions

    Safety instructions Cerabar S PMP71 with 4 to 20 mA HART Safety instructions Designated use The Cerabar S is a pressure transmitter for measuring pressure. The manufacturer accepts no liability for damages resulting from incorrect use or use other than that designated.
  • Page 5: Notes On Safety Conventions And Icons

    Cerabar S PMP71 with 4 to 20 mA HART Safety instructions Notes on safety conventions and icons In order to highlight safety-related or alternative operating procedures in the manual, the following conventions have been used, each indicated by a corresponding icon in the margin.
  • Page 6: Identification

    Identification Cerabar S PMP71 with 4 to 20 mA HART Identification Device designation 2.1.1 Nameplates Note! • The MWP (maximum working pressure) is specified on the nameplate. This value refers to a reference temperature of 20°C (68°F) or 100°F (38°C) for ANSI flanges.
  • Page 7 Cerabar S PMP71 with 4 to 20 mA HART Identification Devices for use in hazardous areas are fitted with an additional nameplate. Dat.: P01-xMD7xxxx-18-xx-xx-xx-002 Fig. 2: Additional nameplate for devices suitable for use in hazardous areas EC type-examination certificate number Type of protection e.g.
  • Page 8 Identification Cerabar S PMP71 with 4 to 20 mA HART Hygienic stainless steel housing (T17) Order Code: Ser.-No.: Span Mat. Dat.: Bei Sauerstoffeinsatz/for oxygen service: Tmax Pmax P01-XMX7Xxxx-18-xx-xx-xx-001 Fig. 5: Nameplate Device name Manufacturer's address Order code See the specifications on the order confirmation for the meanings of the individual letters and digits.
  • Page 9: Scope Of Delivery

    The device complies with the applicable standards and regulations as listed in the EC Declaration of Conformity and thus complies with the statutory requirements of the EC Directives. Endress+Hauser confirms the successful testing of the device by affixing to it the CE mark.
  • Page 10: Installation

    • To ensure optimal readability of the onsite display, it is possible to rotate the housing up to 380°. → ä 14, "Rotating the housing". • Endress+Hauser offers a mounting bracket for installing on pipes or walls. → ä 13, "Wall and pipe-mounting (optional)".
  • Page 11 Cerabar S PMP71 with 4 to 20 mA HART Installation 3.3.1 Installation instructions Note! • If a heated Cerabar S is cooled during the cleaning (e.g. by cold water), a vacuum develops for a short time, whereby water can penetrate the sensor through the pressure compensation point (1).
  • Page 12 Installation Cerabar S PMP71 with 4 to 20 mA HART Mount Cerabar S with shutoff device above the tapping point so that any condensate can flow into the process. Pressure measurement in steam ➀ ➀ ➁ ➁ ➃ ➂ P01-PMx7xxxx-11-xx-xx-xx-002 Fig.
  • Page 13 The seal is not allowed to press against the process isolating diaphragm as this could affect the measurement result. 3.3.3 Wall and pipe-mounting (optional) Endress+Hauser offers a mounting bracket for installing on pipes or walls. mm (in) P01-xMx5xxxx-06-xx-xx-xx-001 Please note the following when mounting: •...
  • Page 14: Post-Installation Check

    Installation Cerabar S PMP71 with 4 to 20 mA HART 3.3.4 Rotating the housing The housing can be rotated up to 380° by loosening the setscrew. max. 380° P01-PMx7xxxx-17-xx-xx-xx-000 Fig. 10: Aligning the housing – T14 and T15 housing: Loosen setscrew with a 2 mm (0.08 in) Allen key.
  • Page 15: Wiring

    Cerabar S PMP71 with 4 to 20 mA HART Wiring Wiring Connecting the device " Caution! If the operating voltage is > 35 VDC, do not open the cover when energized in wet locations. Hazardous live voltage at the terminals.
  • Page 16 Wiring Cerabar S PMP71 with 4 to 20 mA HART 4.1.1 Connecting devices with Harting connector Han7D + – – Han7D – P01-xxx7xxxx-04-xx-xx-xx-001 Fig. 13: Left: electrical connection for devices with Harting connector Han7D Right: view of the connection at the device 4.1.2...
  • Page 17: Connecting The Measuring Unit

    Cerabar S PMP71 with 4 to 20 mA HART Wiring Connecting the measuring unit 4.2.1 Supply voltage Note! • When using the measuring device in hazardous areas, installation must comply with the corresponding national standards and regulations and the Safety Instructions or Installation or Control Drawings.
  • Page 18 Wiring Cerabar S PMP71 with 4 to 20 mA HART 4.2.3 Load U – 10.5 V U – 11.5 V ➀ ➁ £ £ Lmax Lmax Lmax Lmax 23 mA 23 mA [ ] W [ ] W Test Test...
  • Page 19 FieldCare Commubox FXA291 The Commubox FXA291 connects Endress+Hauser field devices with a CDI interface (= Endress+Hauser common data interface) to the USB port of a personal computer or a notebook. For details, refer to TI00405C/07/EN. Note! You will also require the following accessory for the device: "ToF Adapter FXA291".
  • Page 20: Potential Equalization

    Wiring Cerabar S PMP71 with 4 to 20 mA HART Potential equalization Ex applications: Connect all devices to the local potential equalization system. Observe the applicable regulations. Post-connection check Perform the following checks after completing electrical installation of the device: •...
  • Page 21: Operation

    Cerabar S PMP71 with 4 to 20 mA HART Operation Operation Feature 20 "Output; operation" in the order code provides you with information on the operating options available to you. Versions in the order code Operation 4 to 20 mA HART; external operation, LCD Via onsite display and 3 keys on the exterior of the device 4 to 20 mA HART;...
  • Page 22: Operating Elements

    Operation Cerabar S PMP71 with 4 to 20 mA HART The following table illustrates the symbols that can appear on the onsite display. Four symbols can occur at one time. Symbol Meaning Alarm symbol – Symbol flashing: warning, device continues measuring.
  • Page 23 Cerabar S PMP71 with 4 to 20 mA HART Operation 5.2.2 Function of the operating elements – onsite display not connected Press and hold the key or the key combination for at least 3 seconds to execute the corresponding function. Press the key combination for at least 6 seconds for a reset.
  • Page 24: Onsite Operation - Onsite Display Not Connected

    Operation Cerabar S PMP71 with 4 to 20 mA HART Onsite operation – onsite display not connected Note! /M-DAT module, see Page → ä 27, ® To operate the device with a HistoROM "HistoROM®/M-DAT (optional)". 5.3.1 Pressure measuring mode If no onsite display is connected, the following functions are possible by means of the three keys on the electronic insert or on the exterior of the device: •...
  • Page 25: Onsite Operation

    Cerabar S PMP71 with 4 to 20 mA HART Operation Onsite operation – onsite display connected If the onsite display is connected, the three operating keys are used to navigate through the operating menu → ä 23, "Function of the operating elements – onsite display connected".
  • Page 26 Operation Cerabar S PMP71 with 4 to 20 mA HART 5.4.2 Selecting an option Example: selecting "English" as the language of the menu. Onsite display Operation German is selected as the language. A ✓in front of the menu text indicates the active option.
  • Page 27: HistoromĀ®/M-Dat (Optional)

    Cerabar S PMP71 with 4 to 20 mA HART Operation Onsite display Operation Use "E" to save the new value and exit the editing mode. See next graphic. P01-xxxxxxxx-19-xx-xx-xx-031 The new value for the damping is now 30.0 s. – Jump to the next parameter with "E" .
  • Page 28 Operation Cerabar S PMP71 with 4 to 20 mA HART Note! ® • The HistoROM /M-DAT module may be retrofitted at any time (Order No.: 52027785. ® • The HistoROM data and the data in the device are analyzed once a HistoROM /M-DAT is attached to the electronic insert and power is reestablished to the device.
  • Page 29 Cerabar S PMP71 with 4 to 20 mA HART Operation ® Copying configuration data from a HistoROM /M-DAT to a device: Note! The operation must be unlocked. Disconnect device from supply voltage. ® Attach the HistoROM /M-DAT module to the electronic insert. Configuration data from ®...
  • Page 30 Operation Cerabar S PMP71 with 4 to 20 mA HART ® Copying configuration data from a HistoROM /M-DAT to a device: Note! The operation must be unlocked. Disconnect device from supply voltage. ® Attach the HistoROM /M-DAT module to the electronic insert. Configuration data from ®...
  • Page 31: Operation Via Hart Handheld Terminal

    FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare, you can configure all Endress+Hauser devices as well as devices from other manufacturers that support the FDT standard. Hardware and software requirements can be found on the Internet: www.endress.com →...
  • Page 32 Operation Cerabar S PMP71 with 4 to 20 mA HART The table provides an overview of the locking functions: Locking via View/read Modify/write via Unlocking via parameter Onsite Remote DIP switch Onsite Remote display operation display operation DIP switch Onsite display Remote operation Parameters which refer to how the display appears, e.g.
  • Page 33: Factory Setting (Reset)

    Cerabar S PMP71 with 4 to 20 mA HART Operation Factory setting (reset) By entering a certain code, you can completely, or partially, reset the entries for the parameters to the factory settings. ( For factory settings, refer to Operating Instructions BA00413P "Description of device functions").
  • Page 34: Commissioning

    Commissioning Cerabar S PMP71 with 4 to 20 mA HART Commissioning Warning! • If a pressure smaller than the minimum permitted pressure is present at the device, the messages "E120 Sensor low pressure" and "E727 Sensor pressure error - overrange" are output in succession.
  • Page 35: Position Adjustment

    Cerabar S PMP71 with 4 to 20 mA HART Commissioning 6.2.2 Digital communication In digital communication, the MEASURING MODE parameter is displayed in the QUICK SETUP menus and in the BASIC SETUP function group (OPERATING MENU → SETTINGS → BASIC SETUP).
  • Page 36: Pressure Measurement

    Commissioning Cerabar S PMP71 with 4 to 20 mA HART Pressure measurement 6.4.1 Information on pressure measurement Note! • There is a Quick Setup menu for the measuring mode Pressure which guides you through the most important basic functions. With the setting in the MEASURING MODE parameter, you specify which Quick Setup menu should be displayed.
  • Page 37: Lead Sealing Plan

    Cerabar S PMP71 with 4 to 20 mA HART Commissioning Onsite operation Digital communication SET LRV SET LRV Set the measuring range (enter 4 mA value). Set the measuring range (enter 4 mA value). Specify a pressure value for the lower current value Specify a pressure value for the lower current value (4 mA value).
  • Page 38: Maintenance

    Maintenance Cerabar S PMP71 with 4 to 20 mA HART Maintenance ® Keep the pressure compensation and GORE-TEX filter (1) free from contamination and water. P01-PMC71xxx-17-xx-xx-xx-001 Exterior cleaning Please note the following points when cleaning the device: • The cleaning agents used should not corrode the surface and the seals.
  • Page 39: Troubleshooting

    Cerabar S PMP71 with 4 to 20 mA HART Troubleshooting Troubleshooting Messages The following table lists all the possible messages that can occur. The device makes a distinction between the error types "Alarm", "Warning" and "Error". You may specify whether the device should react as if for an "Alarm" or "Warning" for "Error" messages. See "Message type/NA 64"...
  • Page 40 Troubleshooting Cerabar S PMP71 with 4 to 20 mA HART Code Error type/ Message/description Cause Measure Priority NA 64 116 (W116) Warning C>Download error, repeat – The file is defective. – Use another file. download – During the download, the data are –...
  • Page 41 Cerabar S PMP71 with 4 to 20 mA HART Troubleshooting Code Error type/ Message/description Cause Measure Priority NA 64 620 (E620) Error C>Current output out of range The current is outside the permitted – Check pressure applied, reconfigure range 3.8 to 20.5 mA.
  • Page 42 Troubleshooting Cerabar S PMP71 with 4 to 20 mA HART Code Error type/ Message/description Cause Measure Priority NA 64 710 (W710) Warning B>Set span too small. Not – Values for calibration (e.g. lower- – Adjust calibration to suit sensor. (See allowed.
  • Page 43 Cerabar S PMP71 with 4 to 20 mA HART Troubleshooting Code Error type/ Message/description Cause Measure Priority NA 64 720 (E720) Error C>Sensor under temperature – The temperature measured in the – Increase process temperature/ sensor is smaller than the lower ambient temperature.
  • Page 44 Troubleshooting Cerabar S PMP71 with 4 to 20 mA HART Code Error type/ Message/description Cause Measure Priority NA 64 730 (E730) Error C>LRV user limits exceeded – Pressure measured value has – Check system/pressure measured undershot the value specified for the value.
  • Page 45 Cerabar S PMP71 with 4 to 20 mA HART Troubleshooting Code Error type/ Message/description Cause Measure Priority NA 64 742 (A742) Alarm B>Sensor connection error – Electromagnetic effects are greater – Wait a few minutes. (upload) than specifications in the technical –...
  • Page 46: Response Of Outputs To Errors

    Troubleshooting Cerabar S PMP71 with 4 to 20 mA HART Response of outputs to errors The device makes a distinction between the error types Alarm, Warning and Error. See the following table and → ä 39, "Messages". Output A (Alarm)
  • Page 47 Cerabar S PMP71 with 4 to 20 mA HART Troubleshooting 8.2.1 Configuring current output for an alarm You can configure the current output for the event of an alarm by means of the OUTPUT FAIL MODE, ALT. CURR. OUTPUT and SET MAX. ALARM parameters. These parameters are displayed in the OUTPUT group (menu path: (GROUP SELECTION →) OPERATING MENU →...
  • Page 48: Confirming Messages

    Troubleshooting Cerabar S PMP71 with 4 to 20 mA HART Confirming messages Depending on the settings for the ALARM DISPL. TIME and ACK. ALARM MODE parameters, the following measures should be taken to clear a message: Settings Measures – Rectify cause of the message (→ ä 39).
  • Page 49: Repair

    Cerabar S PMP71 with 4 to 20 mA HART Troubleshooting Repair The Endress+Hauser repair concept provides for measuring devices to have a modular design and that the customer may also carry out repairs (→ ä 50, "Spare Parts"). Note! • For certified devices, please refer to the "Repair of Ex-certified devices" Section.
  • Page 50: Spare Parts

    Troubleshooting Cerabar S PMP71 with 4 to 20 mA HART Spare Parts An overview of the spare parts for your device is available in the internet at www.endress.com. To obtain information on the spare parts, proceed as follows : Go to "www.endress.com" and select your country.
  • Page 51: Return

    The measuring device must be returned if repairs or a factory calibration are required, or if the wrong measuring device has been ordered or delivered. According to legal regulations, Endress+Hauser, as an ISO-certified company, is required to follow certain procedures when handling returned products that are in contact with medium.
  • Page 52: Appendix

    Appendix Cerabar S PMP71 with 4 to 20 mA HART Appendix 10.1 Operating menu for onsite display and digital communication Note! • The entire menu is depicted on the following pages. • The menu has a different structure depending on the measuring mode selected. This means that some function groups are only displayed for one measuring mode.
  • Page 53 Cerabar S PMP71 with 4 to 20 mA HART Appendix Measured value GROUP SELECTION LANGUAGE LEVEL SELECTION QUICK SETUP OPERATING MENU MEASURING MODE MEASURING MODE SETTINGS POSITION ADJUSTMENT BASIC SETUP MEASURING MODE MEASURING MODE Pressure Pressure PRESS. ENG. UNIT POS. INPUT VALUE...
  • Page 54 Appendix Cerabar S PMP71 with 4 to 20 mA HART EXTENDED SETUP SAFETY CONFIRM. DISPLAY OUTPUT Pressure TEMP. ENG UNIT Level (not provided for PMP71 with MID) SAFETY LOCK MENU DESCRIPTOR OUTPUT CURRENT SAFETY PASSWORD MAIN DATA FORMAT CURR. CHARACT.
  • Page 55 Cerabar S PMP71 with 4 to 20 mA HART Appendix TRANSMITTER INFO PROCESS INFO HART DATA TRANSMITTER DATA PROCESS CONNECTION SENSOR DATA PROCESS VALUE PEAK HOLD INDICATOR Pressure BUS ADDRESS DEVICE SERIAL No Pmax PROC. CONN. SENSOR SER. NO. MEASURED VALUE COUNTER:P >...
  • Page 56 Appendix Cerabar S PMP71 with 4 to 20 mA HART OPERATION DIAGNOSTICS SERVICE SIMULATION MESSAGES USER LIMITS SYSTEM 2 ENTER RESET CODE SIMULATION MODE ALARM STATUS Pmin ALARM WINDOW CURR. TRIM 4mA OPERATING HOURS LAST DIAG. CODE Pmax ALARM WINDOW CURR.
  • Page 57 Cerabar S PMP71 with 4 to 20 mA HART Appendix Endress+Hauser...
  • Page 58: Index

    Cerabar S PMP71 with 4 to 20 mA HART Index Index Numerics 4 to 20 mA test signal......17 Pipe mounting .
  • Page 59 Cerabar S PMP71 with 4 to 20 mA HART Index Endress+Hauser...
  • Page 60 www.endress.com/worldwide BA00412P/00/EN/02.12 71185804 CCS/FM+SGML 9 71185804...