Endress+Hauser Cerabar S PMC71 Operating Instructions Manual

Endress+Hauser Cerabar S PMC71 Operating Instructions Manual

Pressure transmitter
Hide thumbs Also See for Cerabar S PMC71:

Advertisement

Operating Instructions

Cerabar S PMC71, PMP71, PMP75
Pressure transmitter
6
BA271P/00/en/08.06
71027246
valid from
Software version 02.10
Hardware version 02.00

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Cerabar S PMC71

  • Page 1: Operating Instructions

    Operating Instructions Cerabar S PMC71, PMP71, PMP75 Pressure transmitter BA271P/00/en/08.06 71027246 valid from Software version 02.10 Hardware version 02.00...
  • Page 2 Overview documentation Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Overview documentation Device Documentation Content Remarks Cerabar S 4...20 mA HART Technical Information TI383P Technical data – The documentation is located on the ToF Tool CD. The CD is enclosed with every device ordered with the "HistoROM/M-DAT"...
  • Page 3: Table Of Contents

    Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Table of contents Table of contents Safety instructions ....4 Trouble-shooting ....52 Designated use .
  • Page 4: Safety Instructions

    Safety instructions Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Safety instructions Designated use The Cerabar S is a pressure transmitter for measuring pressure and level. The manufacturer accepts no liability for damages resulting from incorrect use or use other than that designated.
  • Page 5: Notes On Safety Conventions And Icons

    Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Safety instructions Notes on safety conventions and icons In order to highlight safety-relevant or alternative operating procedures in the manual, the following conventions have been used, each indicated by a corresponding icon in the margin.
  • Page 6: Identification

    Identification Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Identification Device designation 2.1.1 Nameplate Note! • The MWP (maximum working pressure) is specified on the nameplate. This value refers to a reference temperature of 20°C (68°F) or 100°F for ANSI flanges.
  • Page 7 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Identification Devices for use in hazardous areas are fitted with an additional nameplate. Dat.: P01-xMD7xxxx-18-xx-xx-xx-002 Fig. 2: Additional nameplate for devices for hazardous areas EC type examination certificate number Type of protection e.g. II 1/2 G EEx ia IIC T4/T6 Electrical data Safety Instructions number e.g.
  • Page 8 Identification Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Stainless steel housing (T17) Cerabar S Made in Germany, D-79689 Maulburg Order Code: Ser.-No.: Span Mat. Dat.: Bei Sauerstoffeinsatz/for oxygen service: Tmax Pmax P01-PMx7xxxx-18-xx-xx-xx-003 Fig. 4: Nameplate for Cerabar S Order code See the specifications on the order confirmation for the meanings of the individual letters and digits.
  • Page 9: Scope Of Delivery

    The device complies with the applicable standards and regulations as listed in the EC declaration of conformity and thus complies with the statutory requirements of the EC Directives. Endress+Hauser confirms the successful testing of the device by affixing to it the CE mark.
  • Page 10: Installation

    • To ensure optimal readability of the on-site display, it is possible to rotate the housing up to 380°. → See Page 17, Section 3.3.5 "Rotating the housing". • Endress+Hauser offers a mounting bracket for installing on pipes or walls. → See Page 15, Section 3.3.4 "Wall and pipe mounting".
  • Page 11 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Installation Pressure measurement in gases ➀ ➁ P01-PMx7xxxx-11-xx-xx-xx-001 Fig. 5: Measuring arrangement for pressure measurement in gases Cerabar S Shut-off device • Mount Cerabar S with shut-off device above the tapping point so that the condensate can flow into the process.
  • Page 12 Installation Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Pressure measurement in liquids ➀ ➁ P01-PMx7xxxx-11-xx-xx-xx-003 Fig. 7: Measuring arrangement for pressure measurement in liquids Cerabar S Shut-off device • Mount Cerabar S with shut-off device below or at the same level as the tapping point.
  • Page 13 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Installation 3.3.2 Installation instructions for devices with diaphragm seals – PMP75 Note! • The Cerabar S with diaphragm seal is screwed in, flanged or clamped, depending on the type of diaphragm seal.
  • Page 14 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Mounting with temperature separator P01-PMx7xxxx-11-xx-xx-xx-005 Endress+Hauser recommends the use of temperature separators in the event of constant extreme fluid temperatures which lead to the maximum permissible electronics temperature of +85°C (+185°F) being exceeded.
  • Page 15 Technical Information TI383P Cerabar S) 3.3.5 Wall and pipe-mounting (optional) Endress+Hauser offers a mounting bracket for installing on pipes or walls. P01-PMx7xxxx-06-xx-xx-xx-001 Please note the following when mounting: • The cable entry should always point downwards so that moisture on the connecting cable can drain off and not penetrate the housing.
  • Page 16 For the "U1 Prepared for diaphragm seal mount" version in feature 70 "Process connection; Material" in the order code of up to including 40 bar-sensors, Endress+Hauser recommends welding on the diaphragm seal as follows: the total welding depth of the fillet weld is 1 mm at an external diameter of 16 mm.
  • Page 17: Post-Installation Check

    Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Installation 3.3.7 Rotating the housing The housing can be rotated up to 380° by loosening the Allen screw. max. 380° P01-PMx7xxxx-17-xx-xx-xx-000 Fig. 14: Aligning the housing – For aluminium and stainless steel housing (T14): Loosen setscrew with a 2 mm Allen key.
  • Page 18: Wiring

    Wiring Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Wiring Connecting the device Note! • When using the measuring device in hazardous areas, installation must comply with the corresponding national standards and regulations and the Safety Instructions or Installation or Control Drawings.
  • Page 19 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Wiring 4.1.1 Connecting devices with Harting plug Han7D Cerabar S + – – Han7D – P01-PMx7xxxx-04-xx-xx-xx-001 Fig. 17: Left: electrical connection for devices with Harting plug Han7D Right: view of the plug at the device 4.1.2...
  • Page 20: Connecting The Measuring Unit

    Wiring Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Connecting the measuring unit 4.2.1 Supply voltage Note! • All explosion protection data are given in separate documentation which is available upon request. The Ex documentation is supplied as standard with all devices approved for use in explosion hazardous areas.
  • Page 21 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Wiring 4.2.3 Load U – 10.5 V U – 11.5 V ➀ ➁ ≤ ≤ Lmax Lmax Lmax 23 mA Lmax 23 mA [ ] Ω [ ] Ω Test Test...
  • Page 22 Wiring Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART 4.2.5 Connecting HART handheld terminal With a HART handheld terminal you can set and check the transmitter and avail of additional functions all along the 4...20 mA line. ➀ min. 250 Ω...
  • Page 23: Potential Matching

    (RS 232C) using the HART protocol. This allows remote operation of the measuring transmitter using Endress+Hauser's operating programs ToF Tool and FieldCare. The Commubox is supplied with power through the serial interface. The Commubox is also suitable for connection to intrinsically safe circuits.
  • Page 24: Overvoltage Protection (Optional)

    Wiring Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Overvoltage protection (optional) Devices showing version "M" in feature 100 "Additional options 1" or feature 110 "Additional options 2" in the order code are equipped with overvoltage protection (see also Technical Information TI382P "Ordering information".
  • Page 25: Operation

    Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Operation Operation Feature 20 "Output; operation" in the order code provides you with information on the operating options available to you. Versions in the order code Operation 4...20 mA HART; external operation, LCD Via on-site display and 3 keys on the exterior of the device 4...20 mA HART;...
  • Page 26: Operating Elements

    Operation Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART The following table illustrates the symbols that can appear on the on-site display. Four symbols can occur at one time. Symbol Meaning Alarm symbol – Symbol flashing: warning, device continues measuring.
  • Page 27 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Operation 5.2.2 Function of the operating elements – on-site display not connected Press and hold the key or the key combination for at least 3 seconds to execute the corresponding function. Press the key combination for at least 6 seconds for a reset.
  • Page 28 Operation Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART 5.2.3 Function of the operating elements – on-site display connected Operating key(s) Meaning – Navigate upwards in the picklist – Edit the numerical values and characters within a function – Navigate downwards in the picklist –...
  • Page 29: On-Site Operation - On-Site Display Not Connected

    Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Operation On-site operation – on-site display not connected Note! ® ® To operate the device with a HistoROM /M-DAT module see Page 34, Section 5.5 "HistoROM M-DAT module". 5.3.1 Pressure measuring mode...
  • Page 30 Operation Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART 5.3.2 Level measuring mode If no on-site display is connected, the following functions are possible by means of the three keys on the electronic insert or on the exterior of the device: •...
  • Page 31 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Operation Carry out position adjustment. Setting lower pressure value. Setting upper pressure value. Pressure is present at device. Desired pressure for lower pressure Desired pressure for upper pressure value (EMPTY PRESSURE...
  • Page 32: On-Site Operation - On-Site Display Connected

    Operation Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART On-site operation – on-site display connected If the on-site display is connected, the three operating keys are used to navigate through the operating menu, → see Page 28, Section 5.2.3 "Function of the operating elements".
  • Page 33 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Operation 5.4.2 Selecting an option Example: select "English" as the language of the menu. On-site display Operation German is selected as the language. A in front of the menu text indicates the active option.
  • Page 34: HistoromĀ®/M-Dat (Optional)

    Operation Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART On-site display Operation Use "E" to save the new value and exit the editing mode. →See next graphic. P01-xxxxxxxx-19-xx-xx-xx-031 The new value for the damping is now 30.0 s. – Jump to the next parameter with "E".
  • Page 35 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Operation Note! ® • The HistoROM /M-DAT module may be retrofitted at any time (Order No.: 52027785). ® • The HistoROM data and the data in the device are analysed once a HistoROM /M-DAT is attached to the electronic insert and power is reestablished to the device.
  • Page 36 Operation Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART ® Copying configuration data from a HistoROM /M-DAT to a device: Note! The operation must be unlocked. Disconnect device from supply voltage. ® Attach the HistoROM /M-DAT module to the electronic insert. Configuration data from ®...
  • Page 37 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Operation ® Copying configuration data from a HistoROM /M-DAT to a device: Note! The operation must be unlocked. Disconnect device from supply voltage. ® Attach the HistoROM /M-DAT module to the electronic insert. Configuration data from ®...
  • Page 38: Operation Via Hart Handheld Terminal

    FieldCare FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare, you can configure all Endress+Hauser devices as well as devices from other manufacturers that support the FDT standard. The following operating systems are supported: WinNT4.0, Win2000 and Windows XP.
  • Page 39: Tof Tool Operating Program

    ToF Tool operating program The ToF Tool is a graphic and menu-guided operating program for measuring devices from Endress+Hauser. It is used for supporting the commissioning, data storage, signal analysis and documentation of the devices. The following operating systems are supported: WinNT4.0, Win2000 and Windows XP.
  • Page 40: Locking/Unlocking Operation

    Operation Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Locking/unlocking operation Once you have entered all the parameters, you can lock your entries against unauthorised and undesired access. You have the following possibilities for locking/unlocking the operation: • Via a DIP-switch on the electronic insert, locally on the display.
  • Page 41: Factory Setting (Reset)

    Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Operation 5.9.2 Locking/unlocking operation via on-site display or remote operation Description Locking operation 1. Select INSERT PIN NO. parameter, Menu path: OPERATING MENU → OPERATION → INSERT PIN NO. 2. To lock operation, enter a number for this parameter between 0...9999 that is ≠100.
  • Page 42 Operation Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Reset code Description and effect 7864 Total reset – Affects the following parameters: – Function group POSITION ADJUSTMENT – Function group BASIC SETUP – Function group EXTENDED SETUP – Function group LINEARISATION (an existing linearisation table is erased) –...
  • Page 43: Commissioning

    Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Commissioning Commissioning Warning! • If a pressure smaller than the minimum permitted pressure is present at the device, the messages "E120 Sensor low pressure" and "E727 Sensor pressure error - overrange" are output in succession.
  • Page 44 Commissioning Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART 6.2.2 ToF Tool, FieldCare or HART handheld terminal The MEASURING MODE parameter is displayed in the ToF Tool and in the HART handheld terminal in the QUICK SETUP menus and in the BASIC SETUP function group (OPERATING MENU →...
  • Page 45: Position Adjustment

    Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Commissioning Position adjustment Due to the orientation of the device, there may be a shift in the measured value, i.e. when the container is empty, the measured value parameter does not display zero. There are three options to choose from when performing position adjustment.
  • Page 46: Pressure Measurement

    Commissioning Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Pressure measurement 6.4.1 Information on pressure measurement Note! • There is a Quick Setup menu for each of the measuring modes Pressure and Level which guides you through the most important basic functions. With the setting in the MEASURING MODE parameter, you specify which Quick Setup menu should be displayed.
  • Page 47 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Commissioning On-site operation ToF Tool, FieldCare and HART handheld terminal POS. ZERO ADJUST (absolute pressure sensors) POS. ZERO ADJUST (absolute pressure sensors) Due to orientation of the device, there may be a shift in Due to orientation of the device, there may be a shift in the measured value.
  • Page 48: Level Measurement

    Commissioning Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Level measurement 6.5.1 Information on level measurement Note! • The Pressure and Level operating modes each have a quick setup menu which guides you through the most important basic functions. → See Page 50 for the "Level" quick setup menu.
  • Page 49 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Commissioning 6.5.2 Overview of level measurement Measuring task LEVEL Measured Description Comment Measured value SELECTION/ variable options display LEVEL MODE The measured variable is LEVEL SELECTION: Via OUTPUT UNIT – Calibration with reference –...
  • Page 50 Commissioning Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART 6.5.3 Quick Setup menu for Level measuring mode Note! • Some parameters are only displayed if other parameters are appropriately configured. For example, the EMPTY CALIB. parameter is only displayed in the following cases: –...
  • Page 51 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Commissioning On-site operation ToF Tool, FieldCare and HART handheld terminal POS. ZERO ADJUST POS. ZERO ADJUST Due to orientation of the device, there may be a shift in Due to orientation of the device, there may be a shift in the measured value.
  • Page 52: Maintenance

    Maintenance Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Maintenance Cerabar S requires no maintenance. Exterior cleaning Please note the following points when cleaning the device: • The cleaning agents used should not attack the surface and the seals.
  • Page 53 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Trouble-shooting Code Error type/ Message/description Cause Measure Priority NA 64 101 (A101) Alarm B>Sensor electronic EEPROM – Electromagnetic effects are greater – Wait a few minutes. error than specifications in the technical –...
  • Page 54 Trouble-shooting Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Code Error type/ Message/description Cause Measure Priority NA 64 132 (A132) Alarm B>Checksum error in totalizer – Main electronics defect. – Replace main electronics. EEPROM 133 (A133) Alarm B>Checksum error in History –...
  • Page 55 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Trouble-shooting Code Error type/ Message/description Cause Measure Priority NA 64 705 (A705) Alarm B>Measurement error – Fault in the main electronics. – Briefly disconnect device from the power supply. – Main electronics defect.
  • Page 56 Trouble-shooting Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Code Error type/ Message/description Cause Measure Priority NA 64 716 (E716) Error B>Sensor diaphragm broken – Sensor defect. – Replace sensor. Factory setting: Alarm 717 (E717) Error C>Transmitter over temperature –...
  • Page 57 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Trouble-shooting Code Error type/ Message/description Cause Measure Priority NA 64 727 (E727) Error C>Sensor pressure error - – Electromagnetic effects are greater – Block off electromagnetic effects or overrange than specifications in the technical eliminate source of disturbance.
  • Page 58 Trouble-shooting Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Code Error type/ Message/description Cause Measure Priority NA 64 738 (A738) Alarm B>Measurement error – Fault in the main electronics. – Briefly disconnect device from the power supply. – Main electronics defect.
  • Page 59: Response Of Outputs To Errors

    Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Trouble-shooting Code Error type/ Message/description Cause Measure Priority NA 64 748 (A748) Alarm B>Memory failure in signal – Electromagnetic effects are greater – Block off electromagnetic effects or processor than specifications in the technical eliminate source of disturbance.
  • Page 60 Trouble-shooting Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART 8.2.1 Configuring current output for an alarm You can configure the current output for the event of an alarm by means of the OUTPUT FAIL MODE, ALT. CURR. OUTPUT and SET MAX. ALARM parameters. These parameters are displayed in the OUTPUT group (menu path: (GROUP SELECTION →) OPERATING MENU →...
  • Page 61: Confirming Messages

    Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Trouble-shooting Confirming messages Depending on the settings for the ALARM DISPL. TIME and ACK. ALARM MODE parameters, the following measures should be taken to clear a message: Settings Measures – ALARM DISPL. TIME = 0 s –...
  • Page 62: Repair

    Section "Spare parts" contains all the spare parts listed with their order numbers. You can order them from Endress+Hauser for repairs on your Cerabar S. As far as necessary, the spare parts also include replacement instructions.
  • Page 63: Spare Parts

    Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Trouble-shooting Spare Parts The following pages list all the spare parts with order numbers which you can order from Endress+Hauser to repair the Cerabar S. When ordering spare parts, always quote the serial number indicated on the nameplate. The spare parts number is embossed on every spare part.
  • Page 64 Trouble-shooting Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART 8.6.1 Spare parts for PMC71, PMP71, PMP75 See the following pages for process connections and sensors. Aluminium or stainless steel housing (T14) P01-FMB70xxx-09-xx-xx-xx-001 Fig. 34: Spare parts for aluminium housing (T14), order number see Page 66...
  • Page 65 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Trouble-shooting Stainless steel housing (T17) P01-FMB70xxx-09-xx-xx-xx-003 Fig. 35: Spare parts for stainless steel housing (T17), order number see Page 66 Endress+Hauser...
  • Page 66 Trouble-shooting Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Mounting set housing/sensor 52020440 Mounting set housing/sensor consists of: 2 O-rings 45.69x2.62 EPDM + retaining ring 71020596 Mounting set housing T17/sensor consists of: 1 O-ring EPDM, 1 molded sealing ring EPDM + retaining ring...
  • Page 67 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Trouble-shooting 8.6.2 Spare parts for PMC71 P01-PMC71xxx-09-xx-xx-xx-000 Process adapter PMC71 52020215 Thread JIS B0202 PF 1/2 (external), AISI 316L 52020216 Thread ISO 228 G 1/2 A G 1/4 (internal), AISI 316L 52020217 Thread ISO 228 G 1/2 A hole 11.4 mm, AISI 316L...
  • Page 68 Trouble-shooting Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Sensor module for Cerabar S PMC71 Approval: For non-hazardous areas ATEX II 1/2 G EEx ia IIC T6 ATEX II 1/2 G EEx ia IIC T6, Overspill protection WHG ATEX II 1/2 D...
  • Page 69 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Trouble-shooting Sensor module for Cerabar S PMC71 (continuation) Process connection, material Thread, inner diaphragm Thread ANSI 1/2 MNPT 1/4 FNPT, AISI 316L Thread ANSI 1/2 MNPT 1/4 FNPT, Alloy C Thread ANSI 1/2 MNPT 1/4 FNPT, Monel Thread ANSI 1/2 MNPT hole 11.4 mm, AISI 316L...
  • Page 70 Trouble-shooting Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Sensor module for Cerabar S PMC71 (continuation) Process connection, material Thread, inner diaphragm Hygienic connections DIN 11851 DN 40 PN 25, AISI 316L, 3A with seal HNBR/EPDM DIN 11851 DN 50 PN 25, AISI 316L, 3A with seal HNBR/EPDM Tri-Clamp ISO 2852 DN 51 (2"), AISI 316L, 3A with seal HNBR/EPDM...
  • Page 71 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Trouble-shooting 8.6.3 Spare parts for PMP71 P01-PMP71xxx-09-xx-xx-xx-000 Sensor module for Cerabar S PMP71 Approval: For non-hazardous areas ATEX II 1/2 G EEx ia IIC T6 ATEX II 1/2 G EEx ia IIC T6, Overspill protection WHG...
  • Page 72 Trouble-shooting Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Sensor module for Cerabar S PMP71 (continuation) Sensor range; OPL (continued): Sensors for gauge pressure Measurement limits: –100 % (–1 bar)...+100 % of sensor nominal range Sensor nominal value (URL) OPL (Over pressure limit) 100 mbar/10 kPa/1.5 psi g...
  • Page 73 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Trouble-shooting Sensor module for Cerabar S PMP71 (continuation) Process connection; material (continued): Thread, flush-mounted diaphragm Thread ISO 228 G 1/2 A, DIN 3852, AISI 316L Thread ISO 228 G 1/2 A, DIN 3852, Alloy C...
  • Page 74: Returning The Device

    • Please fill out completely and sign the "Declaration of Hazardous Material and De- Contamination". It is only then possible for Endress+Hauser to inspect or repair the returned device. • The chemical and physical properties of the fluid. • A description of the application.
  • Page 75: Software History

    Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Trouble-shooting Software history Date of issue Software version Changes software Order code 10.2003 01.00 Original software. 52020517 Compatible with: – ToF Tool Field Tool Package, version 1.04.00 or higher – Commuwin II version 2.08.-1, Update G or higher –...
  • Page 76: Technical Data

    Technical data Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Technical data For technical data, please refer to the Technical Information TI383P for Cerabar S. → See also Page 2, Section "Overview documentation". Appendix 10.1 Operating menu for on-site display, ToF Tool,...
  • Page 77 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Appendix Measured value GROUP SELECTION LANGUAGE LEVEL SELECTION QUICK SETUP OPERATING MENU MEASURING MODE MEASURING MODE SETTINGS POSITION ADJUSTMENT MEASURING MODE Pressure Level POS. ZERO ADJUST LEVEL SELECTION POS. ZERO ADJUST POS.
  • Page 78 Appendix Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART BASIC SETUP MEASURING MODE Pressure Level PRESS. ENG. UNIT LEVEL SELECTION CUSTOMER UNIT P Level Easy Pressure Level Easy Height Level Standard CUST. UNIT FACT. P PRESS. ENG. UNIT PRESS. ENG. UNIT...
  • Page 79 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Appendix Continuation BASIC SETUP "Level", Height Volume Mass see also the previous page LEVEL SELECTION = HEIGHT UNIT UNIT VOLUME MASS UNIT Level Standard CUSTOMER UNIT V CUSTOMER UNIT M CUTOMER UNIT H PRESS.
  • Page 80 Appendix Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART EXTENDED SETUP LINEARISATION LINEARISATION Level measuring Level measuring mode only mode only Display via on-site Display via ToF Tool or display only HART handheld terminal only Pressure Level TEMP. ENG UNIT TEMP.
  • Page 81 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Appendix SAFETY CONFIRM. DISPLAY OUTPUT SAFETY LOCK MENU DESCRIPTOR OUTPUT CURRENT SAFETY PASSWORD MAIN DATA FORMAT CURR. CHARACT. OUTPUT FAIL MODE DIGIT SETS ALTERNATE DATA CURRENT OUTPUT LANGUAGE ALT. CURR. OUTPUT ACK.
  • Page 82 Appendix Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART TRANSMITTER INFO PROCESS INFO HART DATA TRANSMITTER DATA PROCESS CONNECTION SENSOR DATA PROCESS VALUE PEAK HOLD INDICATOR Level Pressure BUS ADDRESS DEVICE SERIAL No Pmax PROC. CONN. SENSOR SER. NO.
  • Page 83 Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Appendix OPERATION DIAGNOSTICS SERVICE SIMULATION MESSAGES USER LIMITS SYSTEM 2 ENTER RESET CODE SIMULATION MODE ALARM STATUS Pmin ALARM WINDOW CURR. TRIM 4mA OPERATING HOURS LAST DIAG. CODE Pmax ALARM WINDOW CURR.
  • Page 84: Patents

    Appendix Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART 10.2 Patents This product may be protected by at least one of the following patents. Further patents are pending. • US 5,836,063 A1 i EP 0 797 084 B1 • US 5,877,424 A1 i EP 0 780 674 B1 •...
  • Page 85: Index

    Cerabar S PMC71, PMP71, PMP75 with 4...20 mA HART Index Index Numerics 4...20 mA test signal ......20 On-site display.
  • Page 87 Erklärung zur Kontamination und Reinigung Please reference the Return Authorization Number (RA#), obtained from Endress+Hauser, on all paperwork and mark the RA# clearly on the outside of the box. If this procedure is not followed, it may result in the refusal of the package at our facility.
  • Page 88 www.endress.com/worldwide BA271P/00/en/08.06 71027246 CCS/FM+SGML6.0 71027246...