Fluke DTX-1800 Technical Reference Handbook page 150

Dtx series cable analyzer
Hide thumbs Also See for DTX-1800:
Table of Contents

Advertisement

DTX Series CableAnalyzer
Technical Reference Handbook
NEXT, PS NEXT, ACR-F, PS ACR-F gives FAIL, FAIL*, or PASS* result
Excessive untwisting of pairs at connector
Poor quality patch cords
Poor quality connectors
Poor quality cable
Poorly matched plug and jack (6A/Class E
Incorrect link interface adapter
Cable compression (tight cable ties, pinches, kinks, etc.)
Inappropriate use of couplers
Excessive noise source near cabling under test. Use the
impulse noise test to check for noise.
Wrong test standard selected
Impulse noise is detected
Electrical devices near the cabling are generating noise pulses.
There is an active link in the same bundle as the cabling under test.
Verify that the tester and smart remote are operating correctly. Connect the units together and run an Autotest.
6-6
Table 6-1. Diagnosing Twisted Pair Test Failures (cont.)
applications)
A
Fixing NEXT problems usually corrects ACR-F
problems.
Tip: The HDTDX test in Single Test mode features a
scanning function that runs the HDTDX test
continuously. This function can be helpful for locating
crosstalk faults caused by cable compression and noise
sources. See page 6-7.
Note