3-1-4 Setting Switch

After changing the "Setting" switch, follow the procedure described below.
After changing the "Setting" switch, turn off the AC input and pull off the AC input plug ,
wait until the status indicator is completely OFF, and then turn on the AC input.
Use a fine-pointed tool such as a small screwdriver to maneuver the switch's lever.
●Setting switch function list
ON
●Setting for beeper sound in the event of power failure, etc. ("Setting"
switch 1)
OFF:The beeper sounds when an alarm is necessary.
ON:The beeper does not sound for backup operation or battery replacement. The beeper
sounds for other errors (connection capacity exceeded, operation error, etc.).
BU150R
3-1 The name and function for the operation and display
Bit
Function to set
1
Beeper sound in the
event of power
failure, etc.
2
Auto startup after
recovery from
power failure
3
ON/OFF the test
once every 4 weeks
4
Auto startup mode
by BS signal
5
BS signal range
6
Logic of Remote
on/off signal
7
8
Select AC input plug
Factory setting: OFF
3 Check and start operation
OFF side
Beeper
sounds
Auto startup
is performed
Test is
performed
Mode A
Always
enabled
Normally
opened
15Aplug
ON side
Beeper
does not
sound
Auto startup
is not
performed
Test is not
performed
Mode B
3
Enabled for
backup
operation
only
Normally
closed
20APlug
35