2 Installation and connection
2-2 How to connect devices to back up
■Group-based control of "power supply output"
When the attached automatic shutdown software is used, you can use the power supply
output group-based control function.
The power supply output receptacles of the UPS are divided into three groups, Groups A, B,
and C.
• Each of "power supply output" Groups B and C can delay its output start time or hasten
its output stop time independently of "power supply output" Group A.
• The output start and stop time control function can be controlled by the automatic
shutdown software "PowerAct Pro" or "SNMP/Web card".
• While the UPS is running, ON/OFF control can be performed on power supply output
from the automatic shutdown software.
• The above delay setting and ON/OFF control can be performed on each of "power
supply output" Groups B and C independently.
The order in which such equipment as servers and peripherals starts up can be set by
using this function.
In addition, forcible ON/OFF control on an output receptacle can be remotely performed.
■Fixing power cables
A connected power cable can be fixed with a retaining clip (BUX150R) provided as an
option.
This clip prevents an input plug from being detached in such a case as when the cable is
pulled.
30
Output ON
Power supply output
Time setting
group A
Power supply output
group B
Time setting
Power supply output
group C
Output OFF
Time setting
Time setting
BU150R