Backup Operation Time Setting / Battery Replacement Mode Selection Switch - Omron S8BA-24D24D480SBF User Manual

Hide thumbs Also See for S8BA-24D24D480SBF:
Table of Contents

Advertisement

4-1-2
Backup operation time setting / Battery replacement mode selec-
tion switch
Switching to the backup operation time setting / Battery
replacement mode
Sets the backup operation time.
For the setting, use a 2.5 mm or less flat-head screwdriver.
Set value
SV FREE
0.5
1
2
3
5
10
15
20
BATT REP
S8BA-series Uninterruptible Power Supply (UPS) User's Manual (U726)
Maximum (back up until battery runs out)
30 seconds
1 min.
2 min.
3 min.
5 min.
10 min.
15 min.
20 min.
Switches to the battery replacement mode.
Set at the time of replacing the battery unit.
Description
4 Operations
4
4 - 5

Advertisement