3-1 The name and function for the operation and display
●Auto startup setting after recovery from power failure ("Setting" switch 2)
OFF : Automatically starts when power is restored.
ON: Does not automatically start when power is restored.
●Setting for whether or not to perform test once every 4 weeks ("Setting"
switch 3)
OFF: The self-diagnostic test is automatically executed once every 4 weeks.
ON:Does not perform the auto test once every 4 weeks.
●Auto startup mode setting ("Setting" switch 4)
OFF: Mode A
ON: Mode B
36
Factory setting: OFF
After a power failure occurs and the unit shuts down using the shutdown software or
contact signal(BS signal), the unit automatically starts and begins to output when the
commercial power is restored.
After the unit is shut down with the UPS monitoring software or contact signal (BS
signal), it does not start up when commercial power is restored. Startup is performed
by turning the "Power" switch OFF once, and then back ON again.
Factory setting: OFF
Use this setting to disable Battery Mode for the regularly performed test.
Factory setting: OFF
After UPS stopped, the UPS is automatically started immediately when "ON" is
detected for the AC input.
After UPS stopped, the UPS is automatically started in the AC input's "OFF to ON"
timing that is detected.
(Definition of AC input OFF: When AC input is OFF for 1 second or more)