Software Updates; Manufacturer Authorization; Completing The Installation; Point Types And Point Evaluation - Bosch ICP-MAP5000-2 Installation Manual

Map 5000 series main panel intrusion alarm system
Hide thumbs Also See for ICP-MAP5000-2:
Table of Contents

Advertisement

60
en | Initial set-up and programming
1.
2.
3.
P
4.3.2

Software updates

All system modules are updated by means of the programming software RPS for MAP.
4
4.3.3

Manufacturer authorization

In order to transfer new software to the system modules with RPS for MAP, a manufacturer
authorization may be needed on the panel side.
1.
2.
3.
4.
4.4

Completing the installation

1.
2.
Systems in accordance with VdS class C and EN 50131
1.
2.
4.5

Point types and point evaluation

Overview of the Standard Point Types and their pre-set properties
Point Type
Bolt Contact
Duress
Fire
Hold-up
Intrusion
2016.06 | 17 | F.01U.168.332
Make a connection to the panel.
Click on the MAP 5000 Panel node.
The software version is displayed in the Properties field under Control Panel Firmware
Version.
Click successively on the system modules in the Hardware Manager.
The software version is shown in the diagnostics field under Software Version.
The version of the programming software RPS for MAP is displayed during start-up or
under RPS Start>RPS Options>Resources.
To carry out updates, follow the instructions in the file How to update ... on the
manufacturer's CD.
Authorize the manufacturer user by a user with corresponding permissions (see operating
manual, section Manufacturer authorization).
Open the control panel enclosure.
Activate Installer Mode (Installer button, page 67).
Log on at the Installer Control Center with the manufacturer's passcode. Use the user ID
000 and password 234567 when logging on for the first time. These are entered directly
in succession. The manufacturer's password can be changed after successful log-on. The
password 234567 is deactivated as a result.
Stick the type label supplied in the main panel accessory pack on the control panel
enclosure at a location that is easily visible from outside.
Lock the enclosure door after completing all work.
On systems in accordance with VdS class C and EN 50131, screw the door closed on the
lock side with two sheet-metal screws (3.5 mm x 10 mm) from the accessory pack in
order to guarantee sufficient mechanical strength.
Fix the adhesive seal on the lock.
Arming state differentiation
Armed
Yes
Yes
Yes
Yes
Yes
Disarmed
Yes
Yes
Yes
Yes
Yes
Installation manual
Ready to arm
status
IP Armed
consideration
(internal)
Yes
Yes
No
Yes
No
No
No
Yes
Yes
Yes
Bosch Sicherheitssysteme GmbH
MAP 5000

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Icp-map5000-com

Table of Contents