Panasonic MINAS S-series Operating Manual page 77

Ac servo motor driver
Hide thumbs Also See for MINAS S-series:
Table of Contents

Advertisement

Peripheral Equipment
Environment
The servo amplifier should be used under Contamination Level 2 or 1 specified by IEC60664-
1 (housing the amplifier in an IP54 control box).
Power
Power
Single-phase 100V : Single-phase 100 to 115V +10%/-15%, 50/60Hz
Single-phase 200V : Single-phase 200 to 230V +10%/-15%, 50/60Hz
Three-phase 200V : Three-phase 200 to 230V +10%/-15%, 50/60Hz
(1) Use under the environment of Over-voltage Category III specified by IEC60664-1.
(2) The power for interface should be marked CE or appropriate EN Standard type, 12VDC to
24VDC, insulated.
Circuit Breaker
Install a circuit breaker between the power supply and noise filter. The circuit breaker should
be IEC Standard and UL listed
Noise Filter
If several amplifiers are used, and a single noise filter is installed at the power supply, consult
the manufacturer of the noise filter.
Control box
Insulated power
for interface
Circuit
Noise filter
breaker
Surge
absorber
marked.
- App. 3 -
Controller
CN–I/F
AC servo
amplifier
Noise filter for
signal lines
L1
L2
L3
Protective earth (PE)
Noise filter for
signal lines
AC servo
motor
U
V
M
W
E
RE
CN–SIG

Advertisement

Table of Contents
loading

Table of Contents