Function Diagram Modules; Menu Selection "Quick Parameterization" - Siemens 6SE7011-5EP60 Operating Instructions Manual

Simovert masterdrives vector control series frequency converter (ac-ac) compact plus type
Table of Contents

Advertisement

Parameterizing Steps
Function diagram
modules
P060 = 3
P071 = ?
P095 = ?
P095=2 P095=10
P095=11
P097 = ?
9-6
www.aotewell.com
Function diagram modules (function diagrams) are shown after the flow
chart for parameter modules stored in the unit software. On the first few
pages are the :
♦ setpoint and command sources (sheets s1 ... s83), on the following
pages are the
♦ analog outputs and the display parameters (sheet a0) and the
♦ open-loop and closed-loop control types (sheets r0 to r5).
It is therefore possible to put together the function diagrams to exactly
suit the selected combination of setpoint/command source and
open/closed-loop control type. This will give you an overview of the
functionality parameterized in the units and of the necessary
assignment of the terminals.
The function parameters and visualization parameters specified in the
function diagrams are automatically adopted in the user menu
(P060 = 0) and can be visualized or changed there.
The parameter numbers of the user menu are entered in P360.
Reference is made in the function diagrams to the respective function
diagram numbers (Sheet [xxx]) of the detail diagrams (in the
Compendium).

Menu selection "Quick parameterization"

Input unit line voltage in V
AC units: r.m.s. alternating voltage
DC units: DC link voltage
The input is important, e.g. for voltage limitation control
(Vdmax control, P515 = 1)
Enter the motor type
2: Compact asynchronous motor 1PH7 (=1PA6)/1PL6/1PH4
10: Async./Sync. IEC (international Norm)
11: Async./Sync. NEMA (US-Norm)
Enter the code number for the connected motor of type
1PH7(=1PA6)/1PL6/1PH4
(For list see Quick Parameterization)
(Automatic parameter assignment is implemented as soon
as the settings P095 = 2 and P097 > 0 have been made)
sales@aotewell.com
6SE7087-6JP60
Operating Instructions
SIMOVERT MASTERDRIVES
Industry Automation
05.2003
Siemens AG
+86-755-8660-6182

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents