Power Section Definition; Sequence For Performing The Power Section Definition - Siemens 6SE7011-5EP60 Operating Instructions Manual

Simovert masterdrives vector control series frequency converter (ac-ac) compact plus type
Table of Contents

Advertisement

Parameterizing Steps
9.2

Power section definition

WARNING
P060 = 8
P070 = ?
P060 = 1
NOTE
9-4
www.aotewell.com
The power section definition has already been completed in the as-
delivered state. It therefore only needs to be carried out if the CUVP
needs replacing, and is not required under normal circumstances.
During the power section definition, the control electronics is informed
which power section it is working with. This step is necessary for all
Compact, chassis and cabinet type units.
If CUVP boards are changed over between different units without the
power section being re-defined, the unit can be destroyed when it is
connected up to the voltage supply and energized.
The unit has to be switched to the "Power section definition" state for
carrying out the power section definition. This is done by selecting the
"Power section definition" menu. The power section is then defined in
this menu by inputting a code number.
Select "Power section definition" menu
Input the code number for the unit concerned
The code number is allocated to the order numbers (MLFB).
The order number can be read off the unit's rating plate.
The list of units is on the following pages.
Return to parameter menu
Fig. 9-3

Sequence for performing the power section definition

To check the input data, the values for the converter supply voltage in
P071 and the converter current in P072 should be checked after
returning to the parameter menu. They must tally with the data given on
the unit rating plate.
PWE: Parameter value P070
In [A]: Rated output current in Ampere (P072)
Order number
6SE7011-5EP60
6SE7013-0EP60
6SE7015-0EP60
6SE7018-0EP60
6SE7021-0EP60
6SE7021-4EP60
6SE7022-1EP60
6SE7022-7EP60
6SE7023-4EP60
sales@aotewell.com
kW
In [A]
0.5
1.5
1.1
3.0
1.5
5.0
3.0
8.0
4.0
10.0
5.5
14.0
7.5
20.5
11.0
27.0
15.0
34.0
Operating Instructions
Industry Automation
05.2003
PWE
1
3
5
7
9
13
15
17
19
6SE7087-6JP60
Siemens AG
SIMOVERT MASTERDRIVES
+86-755-8660-6182

Hide quick links:

Advertisement

Table of Contents
loading