Technical Data
NOTE
Rating plate
Date of manufacture
12-8
www.aotewell.com
The derating of the permissible rated current for installation altitudes of
over 1000 m and at ambient temperatures below 45 °C is calculated as
follows:
Total derating = Derating
K = K
x K
1
2
It must be borne in mind that total derating must not be greater than 1!
Example:
Altitude: 3000 m
Ambient temperature: 35 °C
→ Total derating = 0.845 x 1.25 = 1.056 (= 1)
6SE7023-4EP60
6SE7023-4EP60-Z
Z=K80
Fig. 12-3
Rating plate
The date of manufacture can be derived as follows:
Character
Year of manufacture:
N
P
R
S
Table 12-4
Assignment of characters to the month and year of manufacture
sales@aotewell.com
x Derating
altitude
ambient temperature
K
= 0.845
1
K
= 1.25
2
F2N62047500032
3Ph 380..480V 37,4A
50/60Hz Zmin=1%
3Ph 0-380..480V 0-500Hz
34A
54,4A (30 s)
Character
2001
1 to 9
2002
O
2003
N
2004
D
Operating Instructions
Industry Automation
05.2003
Unit designation
Year of manufacture
Month of manufacture
Month of manufacture
January to September
October
November
December
6SE7087-6JP60
Siemens AG
SIMOVERT MASTERDRIVES
+86-755-8660-6182