Alarms - Siemens 6SE7011-5EP60 Operating Instructions Manual

Simovert masterdrives vector control series frequency converter (ac-ac) compact plus type
Table of Contents

Advertisement

Faults and Alarms
13.2

Alarms

Number / Alarm
Cause
A001
The calculating time utilization of the CUVC
board is too high
Calculating time
A002
Start of the SIMOLINK ring is not functioning.
SIMOLINK start alarm
A014
The DC link voltage is not equal to 0 when the
simulation mode is selected (P372 = 1).
Simulation active alarm
A015
Parameterizable external alarm input 1 has
been activated.
External alarm 1
A016
Parameterizable external alarm input 2 has
been activated.
External alarm 2
A017
The switch for blocking the inverter pulses (X9
terminal 5-6) has been opened (only for units
SAFE STOP alarm
with Order No. ...-11, ...-21, ...-31, ...-61)
active
A020
An overcurrent condition has occurred.
Overcurrent
A021
An overvoltage condition has occurred.
Overvoltage
13-18
www.aotewell.com
The alarm message is periodically displayed on the PMU by A = alarm/
alarm message and a 3-digit number. An alarm cannot be
acknowledged. It is automatically deleted once the cause has been
eliminated. Several alarms can be present. The alarms are then
displayed one after the other.
When the converter is operated with the OP1S operator control panel,
the alarm is indicated in the lowest operating display line. The red LED
additionally flashes (refer to the OP1S operating instructions).
sales@aotewell.com
Counter-measure
- Observe r829 CalcTimeHdroom
- Increase P357 Sampling Time or
- Reduce P340 Pulse Frequency
- Check the fiber-optic cable ring for
interruptions
- Check whether there is an SLB without
voltage in the ring
- Check whether there is a faulty SLB in the
ring
- Set P372 to 0.
- Reduce DC link voltage (disconnect the
converter from the supply)
Check
- whether the cable to the corresponding
digital input has been interrupted.
- parameter P588 Src No Ext Warn1
Check
- whether the cable to the corresponding
digital input has been interrupted.
- parameter P589 Src No Ext Warn2
Close switch X9 5-6 and thus release the
inverter pulses.
Check the driven load for an overload
condition.
- Are the motor and the converter matched?
- Have the dynamic performance requirements
been exceeded.
Check the supply voltage. The converter
regenerates without regeneration possibility.
6SE7087-6JP60
Operating Instructions
SIMOVERT MASTERDRIVES
Industry Automation
10.2001
Siemens AG
+86-755-8660-6182