6-1 Specifications of Control Terminal

Wire Gauge: 26~16AWG 0.1281-1.318mm
Torque: (A) 5kg-cm [4.31Ib-in.] (0.49Nm) (As shown in figure above)
(B) 8kg-cm [6.94Ib-in.] (0.78Nm) (As shown in figure above)
Wiring precautions:
Reserves 5mm and properly install the wire into the terminal; fasten the installation by a
slotted screwdriver. If the wire is stripped, sort the wire before install into the terminal.
Flathead screwdriver: blade width 3.5mm, tip thickness 0.6mm
In the figure above, the factory setting for S1-SCM is short circuit. The factory setting for
+24V-COM is short circuit and SINK mode (NPN); please refer to Chapter 4 Wiring for more
detail.
Terminals
Terminal Function
Digital control signal common
+24V
(Source)
COM
Digital control signal common (Sink) Common for multi-function input terminals
FWD
Forward-Stop command
REV
Reverse-Stop command
MI1
~
Multi-function input 1~8
MI8
Digital frequency meter
DFM
DCM
Digital frequency signal common
Multi-function Output 1
MO1
(photocoupler)
2
,
+24V 5% 200mA
FWD-DCM:
ON
forward running
OFF
deceleration to stop
REV-DCM:
ON
reverse running
OFF
deceleration to stop
Refer to parameters 02-01~02-08 to program the
multi-function inputs MI1~MI8.
Source mode
ON: the activation current is 3.3 mA 11Vdc
OFF: cut-off voltage
Sink Mode
ON: the activation current is 3.3mA
OFF: cut-off voltage 19Vdc
Regard the pulse voltage as the output monitor signal
DFM
Duty-cycle: 50%
Min. load impedance: 1k /100pf
DCM
Max. current: 30mA
Max. voltage: 30Vdc
The AC motor drive releases various monitor signals, such as
drive in operation, frequency attained and overload indication,
via transistor (open collector).
6-3
Chapter 6 Control Terminals C2000 Series
Factory Setting (NPN mode)
5Vdc
13Vdc