Commissioning/service reports

Commissioning/service reports
Setting and test val-
ues
Static pressure
Supply pressure (flow
pressure)
= for natural gas E
= for natural gas LL
= for LPG
Tick gas type
Carbon dioxide con-
tent CO
2
For natural gas E and
LL
■ at lower output
■ at upper output
For LPG
■ at lower output
■ at upper output
Oxygen content O
■ at lower output
■ at upper output
Carbon monoxide
content CO
■ at lower output
■ at upper output
138
Set value
Date:
By
mbar
max. 57.5
mbar
17.4-25
mbar
17.4-25
mbar
42.5-57.5
% by
7.7-9.2
vol.
% by
7.7-9.2
vol.
% by
9.3-10.9
vol.
% by
9.3-10.9
vol.
2
% by
4.4-6.9
vol.
% by
4.4-6.9
vol.
ppm
< 60
ppm
< 60