Operational faults

8
Operational faults
Malfunctions or faults are indicated by the blinking
is displayed immediately. Press the rotary pushbutton to open the error level. It may be possi-
ble to view several error alarms by turning the rotary pushbutton. As long as an error is
present, error level is displayed, even though it has not been opened by pressing the rotary
pushbutton. In addition, the display is illuminated for 1 second in intervals of 10 seconds
when a fault persists.
TROVIS 5575-000x and TROVIS 5575-001x:
The display is illuminated approximately every 10 seconds for one second when opera-
tional faults occur.
TROVIS 5575-002x:
Version without illuminated display.
In the error level, the error is displayed as specified in the list below.
Note!
After the system code number has been changed, any error alarms are suppressed for
approx. 3 minutes.
8.1

Error list

4
Err 1 = Sensor failure (–> section 8.2)
4
Err 2 = Reset to default setting (–> section 2.5)
4
Err 3 = Disinfection temperature not reached (–> section 6.9)
4
Err 4 = Max. charging temperature reached (–> section 6.2)
4
Err 5 = Error alarms issued by the device bus displayed (–> section 7.11.6)
4
Err 6 = Temperature monitoring alarm (–> section 8.3)
8.2

Sensor failure

According to the error list, sensor failures are indicated by displaying "Err 1" in error level.
For detailed information, exit error level and view the different temperature values in operat-
ing level: each sensor icon displayed together with 3 horizontal lines instead of the measured
value indicates a defective sensor. The following list explains how the controller responds to
the failure of the different sensors.
90
EB 5575 EN