Dhw Circuit Additionally Controlled By A Globe Valve - Samson TROVIS 5575 Mounting And Operating Instructions

Automation system trovis 5500 heating and district heating controller
Table of Contents

Advertisement

Parameters
Lag of storage tank charging pump
Sustained DHW temperature
*
Parameters serve as limitation of the adjustment range for the DHW temperature to be set
at the rotary switch
** Deactivation value T = DHW temperature + hysteresis
*** Charging temperature T = DHW temperature + charging temperature boost

6.1.1 DHW circuit additionally controlled by a globe valve

In system Anl 11.1, the following version with globe valve can be configured instead of the
three-way valve control in the DHW circuit:
Fig. 9 · Schematics of a storage tank system with a globe valve for return flow temperature limitation
Globe valve and temperature sensor VF2 are used exclusively for return flow temperature
limitation in the schematics shown above. The pre-control circuit provides at least the same
flow temperature as in the standard schematic version which is calculated from DHW tem-
perature set point + Charging temperature boost + Primary exchanger control boost set
point.
The functions and parameters of the DHW heating in the storage tank system are upgraded
by the following settings:
Function
DHW circuit additionally controlled by a
globe valve
Parameter
Maximum return flow temperature
WE
Parameter level / Range of values
0.5
PA4 / 0 to 10.0
40 °C
PA4 / 20 to 90 °C
Rk2/Y2
SLP
SF1
VF2
ZP
WW
KW
WE
Configuration
0
CO4 -> F20 - 1
WE
Parameter level / Range of values
65 °C
PA4 / 20 to 90 °C
Functions of the DHW circuit
Control circuit/valve 2
Storage tank charging
pump
Storage sensor 1
Flow sensor 2
Circulation pump
Hot water
Cold water
EB 5575 EN
65