Changing Parameters - Samson TROVIS 5575 Mounting And Operating Instructions

Automation system trovis 5500 heating and district heating controller
Table of Contents

Advertisement

2.3

Changing parameters

Depending on the adjusted system code number and the activated functions, not all parame-
ters listed in the parameter list in the Appendix (–> section 12.2) might be available.
The parameters are grouped by topics:
4
PA1: Heating circuit Rk1 (
4
PA2: Heating circuit Rk2 (
4
PA3: Not used
4
PA4: DHW heating
4
PA5: System-wide functions
4
PA6: Not used
4
PA7: Not used
Proceed as follows:
Switch to configuration and parameter level.
Display shows: 0 0 0 0
q
Set valid key number.
Confirm key number.
Display shows: PA1
q
Select parameter level (-> Fig. 2).
Open parameter level.
q
Select desired parameter.
Activate editing mode for the parameter.
q
Edit the parameter.
Confirm the parameter.
To adjust additional parameters, repeat the steps in the fields highlighted in gray.
q
Select End .
Exit parameter level.
q
Select End .
Return to operating level.
)
)
Start-up
25
EB 5575 EN