Brief Operating Instructions
Levelflex FMP53
FOUNDATION Fieldbus
Guided wave radar
These Instructions are Brief Operating Instructions; they are
not a substitute for the Operating Instructions pertaining to
the device.
Detailed information about the device can be found in the
Operating Instructions and the other documentation:
Available for all device versions via:
– Internet:
www.endress.com/deviceviewer
– Smart phone/tablet: Endress+Hauser Operations App
Solutions
Services

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Levelflex FMP53

  • Page 1 Operating Instructions pertaining to the device. Detailed information about the device can be found in the Operating Instructions and the other documentation: Available for all device versions via: – Internet: www.endress.com/deviceviewer – Smart phone/tablet: Endress+Hauser Operations App...
  • Page 2 Levelflex FMP53 FOUNDATION Fieldbus Order code 00X00-XXXX0XX0XXX Ser. No.: X000X000000 TAG No.: XXX000 Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
  • Page 3: Table Of Contents

    Levelflex FMP53 FOUNDATION Fieldbus Table of contents Table of contents Important document information ..........5 Symbols .
  • Page 4 Table of contents Levelflex FMP53 FOUNDATION Fieldbus 11.7 Configuration of the event behavior according to the FOUNDATION Fieldbus specification FF912 ..Endress+Hauser...
  • Page 5: Important Document Information

    Levelflex FMP53 FOUNDATION Fieldbus Important document information Important document information Symbols 1.1.1 Safety symbols Symbol Meaning DANGER! DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury. WARNING! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in WARNING serious or fatal injury.
  • Page 6 Important document information Levelflex FMP53 FOUNDATION Fieldbus 1.1.4 Symbols for certain types of information Symbol Meaning Symbol Meaning Permitted Preferred Procedures, processes or actions that Procedures, processes or actions that are permitted. are preferred. Forbidden Procedures, processes or actions that Indicates additional information.
  • Page 7: Basic Safety Instructions

    The manufacturer is not liable for damage caused by improper or non-designated use. Verification for borderline cases: ‣ For special measured materials and cleaning agents, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of wetted materials, but does not accept any warranty or liability.
  • Page 8: Workplace Safety

    It meets general safety standards and legal requirements. It also complies with the EC directives listed in the device-specific EC Declaration of Conformity. Endress+Hauser confirms this by affixing the CE mark to the device. Endress+Hauser...
  • Page 9: Product Description

    • Do the nameplate data match the ordering information on the delivery note? • Is the DVD with the operating tool present? If required (see nameplate): Are the Safety Instructions (XA) present? If one of these conditions is not satisfied, contact your Endress+Hauser Sales Center. Endress+Hauser...
  • Page 10: Product Identification

    ): All information about the measuring device is displayed. • Enter the serial number from the nameplates into the Endress+Hauser Operations App or scan the 2-D matrix code (QR code) on the nameplate with the Endress+Hauser Operations App: all the information for the measuring device is displayed.
  • Page 11: Storage, Transport

    Levelflex FMP53 FOUNDATION Fieldbus Storage, Transport Storage, Transport Storage conditions • Permitted storage temperature: –40 to +80 °C (–40 to +176 °F) • Use the original packaging. Transport product to the measuring point WARNING Housing or probe may be damaged or break away.
  • Page 12: Mounting

    Mounting Levelflex FMP53 FOUNDATION Fieldbus Mounting Mounting requirements 6.1.1 Suitable mounting position A0014130  3 Mounting requirements for Levelflex Mounting distances • Distance (A) between wall and rod probe: – for smooth metallic walls: > 50 mm (2 in) – for plastic walls: > 300 mm (12 in) to metallic parts outside the vessel •...
  • Page 13: Mounting The Device

    Levelflex FMP53 FOUNDATION Fieldbus Mounting Mounting the device 6.2.1 Required mounting tools • To shorten rod or coax probes: Saw • For flanges and other process connections: appropriate mounting tools • To turn the housing: Hexagonal wrench 8 mm 6.2.2 Mounting the "Sensor remote"...
  • Page 14 Mounting Levelflex FMP53 FOUNDATION Fieldbus Mounting the electronics housing ø42...60 (1.65...2.36) 140 (5.5) 122 (4.8) 175 (6.9) 158 (6.2) A0014793  4 Mounting the electronics housing using the mounting bracket; dimensions: mm (In) Wall mounting Pipe mounting Connecting the cable Required tools: •...
  • Page 15 Levelflex FMP53 FOUNDATION Fieldbus Mounting 6 Nm (4.42 lbf ft) 3 m (9 ft) / 6 m (19 ft) = 50 mm (2") A0015103 6.2.3 Turning the transmitter housing To provide easier access to the connection compartment or display module, the transmitter housing can be turned: max.
  • Page 16 Mounting Levelflex FMP53 FOUNDATION Fieldbus 6.2.4 Turning the display module 3 mm A0013905 If present: Loosen the screw of the securing clamp of the electronics compartment cover using an Allen key and turn the clamp 90° conterclockwise. Unscrew cover of the electronics compartment from the transmitter housing.
  • Page 17: Post-Installation Check

    Levelflex FMP53 FOUNDATION Fieldbus Mounting Post-installation check Is the device undamaged (visual inspection)? Does the device conform to the measuring point specifications? For example: • Process temperature • Process pressure (refer to the chapter on "Material load curves" of the "Technical Information"...
  • Page 18: Electrical Connection

    Electrical connection Levelflex FMP53 FOUNDATION Fieldbus Electrical connection Connection conditions 7.1.1 Terminal assignment PROFIBUS PA / FOUNDATION Fieldbus A0011341  5 Terminal assignment PROFIBUS PA / FOUNDATION Fieldbus Without integrated overvoltage protection With integrated overvoltage protection Cable screen: Observe cable specifications...
  • Page 19 Levelflex FMP53 FOUNDATION Fieldbus Electrical connection Terminal for potential equalization line Cable entries Overvoltage protection module Endress+Hauser...
  • Page 20 Electrical connection Levelflex FMP53 FOUNDATION Fieldbus 7.1.2 Device plug connectors For the versions with fieldbus plug connector (M12 or 7/8"), the signal line can be connected without opening the housing. Pin assignment of the M12 plug connector Meaning Signal +...
  • Page 21: Power Supply

    Levelflex FMP53 FOUNDATION Fieldbus Electrical connection 7.1.3 Power supply PROFIBUS PA, FOUNDATION Fieldbus "Power supply; Output" "Approval" Terminal voltage E: 2-wire; FOUNDATION Fieldbus, switch output • Non-Ex 9 to 32 V G: 2-wire; PROFIBUS PA, switch output • Ex nA •...
  • Page 22: Connecting The Device

    Electrical connection Levelflex FMP53 FOUNDATION Fieldbus External overvoltage protection HAW562 or HAW569 from Endress+Hauser are suited as external overvoltage protection. For detailed information please refer to the following documents: • HAW562: TI01012K • HAW569: TI01013K Connecting the device WARNING Explosion hazard! ‣...
  • Page 23 Levelflex FMP53 FOUNDATION Fieldbus Electrical connection Strip the cable. Strip the cable ends 10 mm (0.4 in). For stranded cables, also attach wire end ferrules. Firmly tighten the cable glands. A0013837 Connect the cable in accordance with the terminal assignment →  18.
  • Page 24: Post-Connection Check

    Electrical connection Levelflex FMP53 FOUNDATION Fieldbus ≤ 3 (0.12) mm (in) A0013661 Post-connection check Are cables or the device undamaged (visual inspection)? Do the cables comply with the requirements? Do the cables have adequate strain relief? Are all cable glands installed, firmly tightened and correctly sealed? Does the supply voltage match the specifications on the transmitter nameplate? Is the terminal assignment correct →...
  • Page 25: Integration Into A Foundation Fieldbus Network

    Levelflex FMP53 FOUNDATION Fieldbus Integration into a FOUNDATION Fieldbus network Integration into a FOUNDATION Fieldbus network Device Description (DD) You require the following to configure a device and integrate it into an FF network: • An FF configuration program • The Cff file (Common File Format: *.cff) •...
  • Page 26 Integration into a FOUNDATION Fieldbus network Levelflex FMP53 FOUNDATION Fieldbus – EH_Levelflex_xxxxxxxxxx – RESOURCE_xxxxxxxxxxx (RB2) SETUP_ xxxxxxxxxxx (TRDSUP) ADV_SETUP_ xxxxxxxxxxx (TRDASUP) DISPLAY_ xxxxxxxxxxx (TRDDISP) DIAGNOSTIC_ xxxxxxxxxxx (TRDDIAG) EXPERT_CONFIG_ xxxxxxxxxxx (TRDEXP) EXPERT_INFO_ xxxxxxxxxxx (TRDEXPIN) SERVICE_SENSOR_ xxxxxxxxxxx (TRDSRVSB) SERVICE_INFO_ xxxxxxxxxxx (TRDSRVIF) DATA_TRANSFER_...
  • Page 27: Block Model

    Endress+Hauser Guideline BA00062S. The guideline provides an overview of the standard function blocks that are described in FOUNDATION Fieldbus Specifications FF 890 - 894. It is designed to help operators use the blocks implemented in the Endress+Hauser field devices. Endress+Hauser...
  • Page 28: Assignment Of The Measured Values (Channel) In An Ai Block

    Integration into a FOUNDATION Fieldbus network Levelflex FMP53 FOUNDATION Fieldbus 8.4.2 Block configuration when device is delivered Device_01 4841.000 DIAGNOSTIC RESOURCE DISPLAY DATA_TRANSFER SETUP ANALOG_INPUT_1 ADV_SETUP ANALOG_INPUT_2 EXPERT_CONFIG EXPERT_INFO SERVICE_SENSOR SERVICE_INFO ARITHMETIC SIGNAL_CHAR INPUT_SELECTOR INTEGRATOR ANALOG_ALARM A0017217  7 Block configuration when device is delivered...
  • Page 29: Methods

    Levelflex FMP53 FOUNDATION Fieldbus Integration into a FOUNDATION Fieldbus network Channel Measured value 32786 Absolute echo amplitude 32787 Absolute interface amplitude 32856 Distance 32885 Elektronic temperature 32938 Interface linearized 32949 Level linearized 33044 Relative echo amplitude 33045 Relative interface amplitude...
  • Page 30: Commissioning Via Wizard

    Commissioning via wizard Levelflex FMP53 FOUNDATION Fieldbus Commissioning via wizard A wizard guiding the user through the initial setup is available in FieldCare and DeviceCare. Connect the device to FieldCare or DeviceCare (for details refer to the "Operating options" chapter of the Operating Instructions).
  • Page 31: Commissioning (Via Operating Menu)

    Levelflex FMP53 FOUNDATION Fieldbus Commissioning (via operating menu) Commissioning (via operating menu) 10.1 Display and operating module 10.1.1 Display appearance User ABC_ DEFG HIJK LMNO PQRS TUVW A0012635  8 Appearance of the display and operation module for on-site operation Measured value display (1 value max.
  • Page 32 Commissioning (via operating menu) Levelflex FMP53 FOUNDATION Fieldbus 10.1.2 Operating elements Meaning Minus key For menu, submenu Moves the selection bar upwards in a picklist. A0013969 For text and numeric editor In the input mask, moves the selection bar to the left (backwards).
  • Page 33 Levelflex FMP53 FOUNDATION Fieldbus Commissioning (via operating menu) 10.1.3 Opening the context menu Using the context menu, the user can call up the following menus quickly and directly from the operational display: • Setup • Conf. backup disp. • Simulation Calling up and closing the context menu The user is in the operational display.
  • Page 34: Operating Menu

    Commissioning (via operating menu) Levelflex FMP53 FOUNDATION Fieldbus 10.2 Operating menu Parameter/Submenu Meaning Description Language Defines the operating language of the on-site display. Setup When appropriate values have been assigned toall setup parameters, the measured should be completely configured in a standard application.
  • Page 35: Unlock The Device

    Levelflex FMP53 FOUNDATION Fieldbus Commissioning (via operating menu) 10.3 Unlock the device If the device has been locked, it must be unlocked before the measurement can be configured. For details refer to the Operating Instructions of the device: BA01053F (FMP53, FOUNDATION Fieldbus) 10.4...
  • Page 36: Configuration Of A Level Measurement

    Commissioning (via operating menu) Levelflex FMP53 FOUNDATION Fieldbus 10.5 Configuration of a level measurement 20 mA 100% 4 mA A0011360  10 Configuration parameters for level measurements in liquids LN = Length of probe R = Reference point of the measurement...
  • Page 37: User-Specific Applications

    Levelflex FMP53 FOUNDATION Fieldbus Commissioning (block-based operation) Setup → Level  Displays the measured level L. Setup → Distance  Displays the distance D between the reference point R and the level L. 10. Setup → Signal quality  Displays the signal quality of the level echo.
  • Page 38 Commissioning (block-based operation) Levelflex FMP53 FOUNDATION Fieldbus 11.1.3 Configuring the Transducer Blocks The measurement and the display module are configured using the Transducer Blocks. The general procedure is the same for all Transducer Blocks: If necessary, change the block name.
  • Page 39: Scaling Of The Measured Value In An Ai Block

    Levelflex FMP53 FOUNDATION Fieldbus Commissioning (block-based operation) Specify the alarm priorities by means of the High High Priority/HI_HI_PRI, High Priority/ HI_PRI, Low Low Priority/LO_LO_PRI and Low Priority/LO_PRI parameters. Reporting to the field host system only takes place with alarms with a priority greater than 2.
  • Page 40: Language Selection

    Commissioning (block-based operation) Levelflex FMP53 FOUNDATION Fieldbus 11.3 Language selection Step Block Parameter Action DISPLAY (TRDDISP) Language (language) Select language Selection: • 32805: Arabian • 32824: Chinese simplified • 32842: Czech • 32881: Dutch • 32888: English • 32917: French •...
  • Page 41: Configuration Of A Level Measurement

    Levelflex FMP53 FOUNDATION Fieldbus Commissioning (block-based operation) 11.4 Configuration of a level measurement The Setup method can also be used to configure the measurement. It is called up via the SETUP (TRDSUP) transducer block. 20 mA 100% 4 mA A0011360 ...
  • Page 42 Commissioning (block-based operation) Levelflex FMP53 FOUNDATION Fieldbus Step Block Parameter Action SETUP (TRDSUP) Distance unit Select distance unit. (distance_unit) Selection: • 1010: m • 1013: mm • 1018: in • 1019: ft SETUP (TRDSUP) Tank type (tank_type) Select tank type.
  • Page 43: Configuration Of The On-Site Display

    "Tank type" = "Bypass/pipe" If required, lower DCs can ben entered into the "DC value (dc_value)" parameter. However, for DC<1.6 the measuring range may be reduced; for details please contact Endress+Hauser. 11.5 Configuration of the on-site display 11.5.1...
  • Page 44 Commissioning (block-based operation) Levelflex FMP53 FOUNDATION Fieldbus Functions of the parameter options Options Description 33097: Execute backup A backup copy of the current device configuration in the HistoROM is saved to the display module of the device. The backup copy comprises the transmitter data of the device.
  • Page 45 Levelflex FMP53 FOUNDATION Fieldbus Commissioning (block-based operation) 11.7 Configuration of the event behavior according to the FOUNDA- TION Fieldbus specification FF912 The device complies with the FOUNDATION Fieldbus specification FF912. This has - among other things - the following consequences: •...
  • Page 46 Commissioning (block-based operation) Levelflex FMP53 FOUNDATION Fieldbus 11.7.1 Groups of events The diagnostic messages are classified into 16 groups according to the source and severity of the respective event. A default diagnostic category is allocated to each group. Each group is also represented by one bit of the allocation parameters.
  • Page 47 Levelflex FMP53 FOUNDATION Fieldbus Commissioning (block-based operation) Severity of the event Default diagnostic category Source of the Events within the group event Configuration • C411: Up-/download • C431: Trim • C484: Simulation failure mode • C485: Simulation measured value • C491: Simulation current output •...
  • Page 48 Commissioning (block-based operation) Levelflex FMP53 FOUNDATION Fieldbus 11.7.2 Allocation parameters The allocation of event categories to the event groups is controlled by the allocation parameters. They reside in the RESOURCE (RB2) block: • FD_FAIL_MAP: for the Failure (F) event category •...
  • Page 49 Levelflex FMP53 FOUNDATION Fieldbus Commissioning (block-based operation) Example The Highest severity / Configuration group contains the messages 410: Data transfer, 411: Up-/Download, 435: Linearization and 437: Configuration incompatible. These messages are no longer to be classified as Failure (F) but as Funcktion check (C).
  • Page 50 Commissioning (block-based operation) Levelflex FMP53 FOUNDATION Fieldbus  13 Default state of the "Fail Map" and "Check Map" columns Look for the Configuration Highest Severity group in the Fail Map column and deactivate the associated checkbox (A). Activate the respective checkbox in the Check Map column (B).
  • Page 51 Levelflex FMP53 FOUNDATION Fieldbus Commissioning (block-based operation)  14 Changed state of the "Fail Map" and "Check Map" columns Make sure that for each group the corresponding bit is set to 1 in at least one of the allocation parameters. Otherwise no event category is transmitted with the event message.
  • Page 52 Commissioning (block-based operation) Levelflex FMP53 FOUNDATION Fieldbus 11.7.3 Configurable area An event category can be individually defined for the following parameters - irrespective of the group of events they belong to by default. • F941: Echo lost • S942: In safety distance Prior to changing the event category, the event must be allocated to one of the bits 1 to 15.
  • Page 53 Levelflex FMP53 FOUNDATION Fieldbus Commissioning (block-based operation) Select one of these bits (in the example: Configurable Area Bit 1) and select In safety distance from the associated drop-down menu. Confirm the selection by pressing the Enter key. Got to the Offspec Map column and activate the checkbox of the respective bit (in the example: Configurable Area Bit 1).
  • Page 54 Commissioning (block-based operation) Levelflex FMP53 FOUNDATION Fieldbus Suppression of individual events For individual events, the transmission to the bus can suppressed by the use of a mask. The corresponding events will be displayed but not transmitted to the bus. In FieldCare, this mask can be found at Expert →...
  • Page 56 *71293241* 71293241 www.addresses.endress.com...