Brief Operating Instructions
Levelflex FMP55
Guided Level-Radar
These Instructions are Brief Operating Instructions; they do not replace the
Operating Instructions included in the scope of supply.
For detailed information, refer to the Operating Instructions and other
documentation on the CD-ROM provided or visit "www.endress.com/
deviceviewer".
KA01109F/00/EN/02.12
71206487

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Levelflex FMP55

  • Page 1 Brief Operating Instructions Levelflex FMP55 Guided Level-Radar These Instructions are Brief Operating Instructions; they do not replace the Operating Instructions included in the scope of supply. For detailed information, refer to the Operating Instructions and other documentation on the CD-ROM provided or visit "www.endress.com/ deviceviewer".
  • Page 2: Table Of Contents

    Table of contents Levelflex FMP55 Table of contents 1 Important document information .......
  • Page 3: Important Document Information

    Levelflex FMP55 Important document information 10 Commissioning with a FOUNDATION Fieldbus configuration program (block-oriented operation) ........39 10.1 Block configuration .
  • Page 4: Basic Safety Instructions

    The manufacturer is not liable for damage caused by improper or non-designated use. Verification for borderline cases: For special measured materials and cleaning agents, Endress+Hauser is glad to provide ► assistance in verifying the corrosion resistance of wetted materials, but does not accept any warranty or liability.
  • Page 5: Workplace Safety

    It fulfills general safety requirements and legal requirements. It also conforms to the EC directives listed in the device-specific EC declaration of conformity. Endress+Hauser confirms this fact by applying the CE mark. Endress+Hauser...
  • Page 6: Product Description

    Product description Levelflex FMP55 Product description Compact device Levelflex A0012399 Design of the Levelflex å 1 Electronics housing Process connection (here as an example: flange) Rope probe End-of-probe weight Rod probe Coax probe Endress+Hauser...
  • Page 7: Electronics Housing

    Levelflex FMP55 Product description Electronics housing A0012422 Design of the electronics housing å 2 Electronics compartment cover Display module Main electronics module Cable glands (1 or 2, depending on instrument version) Nameplate I/O electronics module Terminals (pluggable spring terminals) Connection compartment cover...
  • Page 8: Incoming Acceptance And Product Identification

    Incoming acceptance and product identification Levelflex FMP55 Incoming acceptance and product identification Incoming acceptance DELIVERY NOTE 1 = 2 A0013696 A0016870 A0013921 A0013922 A0013696 Endress+Hauser...
  • Page 9: Product Identification

    A0013696 A0014038 A0013696 A0014037 If one of the conditions does not comply, contact your Endress+Hauser distributor. Product identification The following options are available for identification of the measuring device: • Nameplate specifications • Order code with breakdown of the device features on the delivery note •...
  • Page 10: Storage, Transport

    Storage, Transport Levelflex FMP55 Order code: Ser. no.: Ext. ord. cd.: A0014103 Example of a nameplate å 3 Order code Serial number (Ser. no.) Extended order code (Ext. ord. cd.) Only 33 digits of the extended order code can be indicated on the nameplate. If the extended order code exceeds 33 digits, the rest will not be shown.
  • Page 11 Levelflex FMP55 Storage, Transport A0013920 NOTICE Shipping lock for FMP5x with coax probe For FMP5x with coax probe the coax tube is not fixed permanently to the electronics ► housing. For shipping and transport it is secured with two cable ties. In order to prevent the spacer at the probe rod from moving along the probe, these cable ties must not be loosened when transporting and mounting the device.
  • Page 12: Mounting

    Mounting Levelflex FMP55 Mounting Suitable mounting position A0011281 • Rod probes / rope probes: must be mounted in a stilling well or bypass (® ä 13) • Coax probes: can be mounted at an arbitrary distance from the wall of the vessel •...
  • Page 13: Special Mounting Conditions

    Levelflex FMP55 Mounting A0012608 Coax probes can be supported at any point of the outer tube. Special mounting conditions 6.3.1 Bypasses and stilling wells For information on bypass solutions from Endress+Hauser please contact your Endress +Hauser sales representative. Endress+Hauser...
  • Page 14 Mounting Levelflex FMP55 A0014129 Mounting in a stilling well Mounting in a bypass • Pipe diameter: > 40 mm (1.6") for rod probes • Rod probe installation can take place up to a diameter size of 100 mm. In the event of larger diameters, a coax probe is recommended.
  • Page 15: Mounting The Device

    Levelflex FMP55 Mounting 6.3.2 Non-metallic vessels When mounting Levelflex in a non-metallic vessel, use a coax probe. Mounting the device 6.4.1 Required mounting tools • For flanges and other process connections: appropriate mounting tools • To turn the housing: Hexagonal wrench 8 mm 6.4.2...
  • Page 16 Mounting Levelflex FMP55 A0012852 When lowering the rope probe into the vessel, observe the following: • Uncoil rope and lower it slowly and carefully into the vessel. • Do not kink the rope. • Avoid any backlash, since this might damage the probe or the vessel fittings.
  • Page 17: Post-Installation Check

    Levelflex FMP55 Mounting 3. Firmly tighten the securing screw. (1,5 Nm for plastics housing; 2,5 Nm for aluminium or stainless steel housing). 6.4.5 Turning the display module 3 mm A0013905 1. Loosen the screw of the securing clamp of the electronics compartment cover using an Allen key and turn the clamp 90°...
  • Page 18: Electrical Connection

    Electrical connection Levelflex FMP55 Electrical connection Connection options 7.1.1 Connection options PROFIBUS PA / FOUNDATION Fieldbus A0011341 Terminal assignment PROFIBUS PA / FOUNDATION Fieldbus å 4 Without integrated overvoltage protection With integrated overvoltage protection Cable screen: Observe cable specifications (® ä 20)
  • Page 19 Levelflex FMP55 Electrical connection Terminal for potential equalization line Cable entries Overvoltage protection module Endress+Hauser...
  • Page 20: Connection Options

    Connection options 7.2.1 Cable specification FOUNDATION Fieldbus • Endress+Hauser recommends using twisted, shielded two-wire cables. • Terminals for wire cross-sections: 0.5 to 2.5 mm (20 to 14 AWG) • Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in) For further information on the cable specifications, see Operating Instructions BA00013S "FOUNDATION Fieldbus Overview", FOUNDATION Fieldbus Guideline and IEC...
  • Page 21: Connection Data

    < 1.5 pF Nominal arrest impulse voltage (8/20 ms) 10 kA External overvoltage protection HAW562 or HAW569 from Endress+Hauser are suited as external overvoltage protection. For detailed information please refer to the following documents: • HAW562: TI01012K • HAW569: TI01013K Connection data 7.3.1...
  • Page 22: Connecting The Measuring Device

    Electrical connection Levelflex FMP55 Connecting the measuring device WARNING Explosion hazard! Comply with the relevant national standards. ► Observe the specifications in the Safety Instructions (XA). ► Only use the specified cable glands. ► Check whether the supply voltage matches the specifications on the nameplate.
  • Page 23 Levelflex FMP55 Electrical connection A0013837 Connect the cable in accordance with the terminal assignment (® ä 18). 8. When using screened cable: Connect the cable screen to the ground terminal. 9. Screw the cover onto the connection compartment. 10. For instruments with safety pin for the lid: Adjust the safety pin so that its edge is over the edge of the display lid.
  • Page 24 Electrical connection Levelflex FMP55 ≤ 3 (0.12) mm (in) A0013661 Endress+Hauser...
  • Page 25: Post-Connection Check

    Levelflex FMP55 Integration into a FOUNDATION Fieldbus network Post-connection check Are cables or the device undamaged (visual inspection)? Do the cables comply with the requirements? Do the cables have adequate strain relief? Are all cable glands installed, firmly tightened and correctly sealed? Does the supply voltage match the specifications on the transmitter nameplate? Is the terminal assignment correct (®...
  • Page 26: Device Identification And Addressing

    Integration into a FOUNDATION Fieldbus network Levelflex FMP55 The device is integrated into the FF network as follows: 1. Start the FF configuration program. 2. Download the Cff and device description files (*.ffo, *.sym (for format 4) *ff5, *sy5 (for format 5) to the system.
  • Page 27 Levelflex FMP55 Integration into a FOUNDATION Fieldbus network – EH_Levelflex_xxxxxxxxxx – RESOURCE_xxxxxxxxxxx (RB2) SETUP_ xxxxxxxxxxx (TRDSUP) ADV_SETUP_ xxxxxxxxxxx (TRDASUP) DISPLAY_ xxxxxxxxxxx (TRDDISP) DIAGNOSTIC_ xxxxxxxxxxx (TRDDIAG) EXPERT_CONFIG_ xxxxxxxxxxx (TRDEXP) EXPERT_INFO_ xxxxxxxxxxx (TRDEXPIN) SERVICE_SENSOR_ xxxxxxxxxxx (TRDSRVSB) SERVICE_INFO_ xxxxxxxxxxx (TRDSRVIF) DATA_TRANSFER_ xxxxxxxxxxx (TRDHROM)
  • Page 28: Block Model

    Endress+Hauser Guideline BA00062S. The guideline provides an overview of the standard function blocks that are described in FOUNDATION Fieldbus Specifications FF 890 - 894. It is designed to help operators use the blocks implemented in the Endress+Hauser field devices. Endress+Hauser...
  • Page 29: Assignment Of The Measured Values (Channel) In An Ai Block

    Levelflex FMP55 Integration into a FOUNDATION Fieldbus network 8.4.2 Block configuration when device is delivered Device_01 4841.000 DIAGNOSTIC RESOURCE DISPLAY DATA_TRANSFER SETUP ANALOG_INPUT_1 ADV_SETUP ANALOG_INPUT_2 EXPERT_CONFIG EXPERT_INFO SERVICE_SENSOR SERVICE_INFO ARITHMETIC SIGNAL_CHAR INPUT_SELECTOR INTEGRATOR ANALOG_ALARM A0017217 Block configuration when device is delivered å...
  • Page 30: Methods

    Integration into a FOUNDATION Fieldbus network Levelflex FMP55 Channel Measured value 32785 Absolute EOP amplitude 32786 Absolute echo amplitude 32787 Absolute interface amplitude 32856 Distance 32885 Elektronic temperature 32938 Interface linearized 32949 Level linearized 33044 Relative echo amplitude 33045 Relative interface amplitude...
  • Page 31: Commissioning Via Operating Menu (On-Site Display, Fieldcare)

    Levelflex FMP55 Commissioning via operating menu (On-site display, FieldCare) Commissioning via operating menu (On-site display, FieldCare) Display and operating module 9.1.1 Display appearance User ABC_ DEFG HIJK LMNO PQRS TUVW A0012635 Appearance of the display and operation module for on-site operation å...
  • Page 32 Commissioning via operating menu (On-site display, FieldCare) Levelflex FMP55 9.1.2 Navigation and selection from a list Use the operating keys to navigate within the operating menu and to select options from a list. Meaning "Minus" key Henceforth represented by S.
  • Page 33: Operating Concept

    Levelflex FMP55 Commissioning via operating menu (On-site display, FieldCare) Operating concept 9.2.1 Structure Language Display/operation Parameter 1 Parameter 2 Parameter N Setup Setup parameter 1 Setup parameter 2 Setup parameter N Advanced setup Enter access code Parameter 1 Parameter N...
  • Page 34 Commissioning via operating menu (On-site display, FieldCare) Levelflex FMP55 9.2.2 Submenus and user roles The submenus are designed for different user roles. A user role is defined by typical tasks within the lifecycle of the device. User role Typical tasks...
  • Page 35: Adjust The Display Contrast

    Levelflex FMP55 Commissioning via operating menu (On-site display, FieldCare) Adjust the display contrast • O + F (pressed simultaneously): increases the contrast. • S + F (pressed simultaneously): decreases the contrast. Unlock the device If the device has been locked, it must be unlocked before the measurement can be configured.
  • Page 36 Commissioning via operating menu (On-site display, FieldCare) Levelflex FMP55 1. Unscrew the lid from the compartment for the display and operating module. 2. Slightly turn the display and operating module to remove it from the compartment. 3. Set the locking switch (WP: Write Protection) into the desired position. (A): unlocked;...
  • Page 37: Set The Operating Language

    Levelflex FMP55 Commissioning via operating menu (On-site display, FieldCare) Set the operating language A0013637 Endress+Hauser...
  • Page 38: Configuration Of An Interface Measurement

    Commissioning via operating menu (On-site display, FieldCare) Levelflex FMP55 Configuration of an interface measurement 100% DK (DC ) A0011177 Configuration parameters for interface measurements å 13 R = Reference pioint of the measurement = Distance of interface (Distance from reference point to lower...
  • Page 39: User-Specific Applications (Operation)

    Levelflex FMP55 Commissioning with a FOUNDATION Fieldbus configuration program (block-oriented operation) Step Parameter Action Setup ® Level Displays the measured level L. Setup ® Interface Displays the interface height L Setup ® Distance Displays the distance D between the reference point R and the level L.
  • Page 40 Commissioning with a FOUNDATION Fieldbus configuration program (block-oriented operation) Levelflex FMP55 4. Load Cff and device description files into the host system or the configuration program. Make sure you are using the right system files. 5. Identify the device using the DEVICE_ID (see Point 2). Assign the desired tag name to the device by means of the Pd-tag/FF_PD_TAG parameter.
  • Page 41: Scaling Of The Measured Value In An Ai Block

    Levelflex FMP55 Commissioning with a FOUNDATION Fieldbus configuration program (block-oriented operation) 4. Use the Transducer Scale/XD_SCALE parameter to select the desired unit and the block input range for the process variable (® ä 41). Make sure that the unit selected suits the process variable selected.
  • Page 42 Commissioning with a FOUNDATION Fieldbus configuration program (block-oriented operation) Levelflex FMP55 XD_SCALE OUT_SCALE EU_100 EU_0 EU_100 EU_0 OUT_VALUE A0017338 Scaling of the measured value in an AI Block å 14 • If you have selected the Direct mode for the L_TYPE parameter, you cannot change the values and units for XD_SCALE and OUT_SCALE.
  • Page 43: Language Selection

    Levelflex FMP55 Commissioning with a FOUNDATION Fieldbus configuration program (block-oriented operation) 10.3 Language selection Step Block Parameter Action DISPLAY (TRDDISP) Language (language) Select language Selection: • 32805: Arabian • 32824: Chinese simplified • 32842: Czech • 32881: Dutch • 32888: English •...
  • Page 44 Commissioning with a FOUNDATION Fieldbus configuration program (block-oriented operation) Levelflex FMP55 100% DK (DC ) A0011177 Configuration parameters for interface measurements å 15 R = Reference pioint of the measurement = Distance of interface (Distance from reference point to lower medium)
  • Page 45 Levelflex FMP55 Commissioning with a FOUNDATION Fieldbus configuration program (block-oriented operation) Step Block Parameter Action SETUP (TRDSUP) Tank type (tank_type) Select tank type. Selection: • 32816: Bypass / pipe • 33288: Metallic • 33302: Coaxial • 33432: Twin rope • 33433: Twin rod •...
  • Page 46: Configuration Of The On-Site Display

    Commissioning with a FOUNDATION Fieldbus configuration program (block-oriented operation) Levelflex FMP55 Step Block Parameter Action SETUP (TRDSUP) Signal quality Displays the signal (signal_quality) quality of the level echo. SETUP (TRDSUP) Confirm distance Compare the displayed (confirm_distance) distance to the real...
  • Page 47: Configuration Management

    Levelflex FMP55 Commissioning with a FOUNDATION Fieldbus configuration program (block-oriented operation) Parameter Factory setting for devices with 1 current Factory setting for devices with 2 current output outputs Value 2 display Level linearized Level linearized Value 3 display Upper interface thickness...
  • Page 48: Protection Of The Settings Against Unauthorized Changes

    Commissioning with a FOUNDATION Fieldbus configuration program (block-oriented operation) Levelflex FMP55 10.7 Protection of the settings against unauthorized changes There are two ways to protect the settings against unauthorized changes: • Via locking switch (hardware locking) (® ä 35) • Via operating menu (software locking) (® ä 36) •...
  • Page 52 *71206487* KA01109F/00/EN/02.12 71206487 71206487 CCS/COSIMA...

This manual is also suitable for:

Levelflex fmp50Levelflex fmp53