User calibration

Calibrates the channel to the default low and high range values for the channel's input type. Refer to the
table for the input type desired.
Step
1
In Wireless Builder, set the transmitter's Write Lock to Unlocked.
2
In Wireless Builder, set the transmitter's channel to OOS (Out of Service).
3
Loosen the M3 locking set screw on the transmitter's battery end-cap (opposite end from
display). Unscrew and remove the end cap.
4
See Figure 2 for terminal connections. If your PV is connected to the channel, disconnect it first,
then connect a calibrator source to the channel's terminals. It is not necessary to disconnect
any jumper wires on the terminals.
5
At the transmitter display, verify the channel's PV value is followed by an out of service (OUT
SVC) message.
Use Authentication Device's Device Local Configuration buttons to navigate to the transmitter's
CAL menu.
If the transmitter is locked a LOCKED message will be displayed. Go to step 1.
If CAL menu is passcode protected, enter the passcode.
If the channel is not out of service a WRONG MODE message will be displayed. Go to step 2.
6
Select the channel for calibration (CH 1, CH 2 or CH 3). Select USER CAL. Follow displayed
instructions.
Using your calibration source, apply the low calibration value indicated on display. For TC
apply cold junction compensated mV value. For RTD apply equivalent resistance value.
Press Enter to accept the value. Display will say BUSY, then CAL LO COMPLETE.
Press Enter to continue.
Apply the high calibration input value indicated on display.
Press Enter to accept the value. Display will say BUSY, then SUCCESS. Otherwise, the
display will show one of the calibration error messages listed in Table 3.
Press Enter to return to PV display.
7
Repeat steps 1 through 6 for each channel you want to calibrate.
8
Reverse steps 3 and 4.
9
When ready, in Wireless Builder return the transmitter's channel to service and set Write Lock
to Locked.
Revision 2
8/7/07

Table 1 User calibration: TC and RTD

OneWireless XYR 6000 Temperature Transmitter User's Manual
3.4. Calibrating the transmitter