General Precaution; Choose Suitable Motor Cable And Precautions; B.2 Amd - Emi Filter Cross Reference - Delta VFD-M-D series User Manual

Specific ac motor drives for the elevator door
Table of Contents

Advertisement

B.2 AMD - EMI Filter Cross Reference

The EMI Filter for VFD004M21B-D is RF015M21AA.
Installation
All electrical equipment, including AC motor drives, will generate high-frequency/low-frequency noise
and will interfere with peripheral equipment by radiation or conduction when in operation. By using an
EMI filter with correct installation, much interference can be eliminated. It is recommended to use
DELTA EMI filter to have the best interference elimination performance.
We assure that it can comply with following rules when AC motor drive and EMI filter are installed and
wired according to user manual:
EN61000-6-4
EN61800-3: 1996 + A11: 2000
EN55011 (1991) Class A Group 1 (1

General precaution

1.
EMI filter and AC motor drive should be installed on the same metal plate.
2.
Please install AC motor drive on footprint EMI filter or install EMI filter as close as possible to
the AC motor drive.
3.
Please wire as short as possible.
4.
Metal plate should be grounded.
5.
The cover of EMI filter and AC motor drive or grounding should be fixed on the metal plate and
the contact area should be as large as possible.

Choose suitable motor cable and precautions

Improper installation and choice of motor cable will affect the performance of EMI filter. Be sure to
observe the following precautions when selecting motor cable.
1.
Use the cable with shielding (double shielding is the best).
2.
The shielding on both ends of the motor cable should be grounded with the minimum length
and maximum contact area.
3.
Remove any paint on metal saddle for good ground contact with the plate and shielding.
Revision Jan. 2007, MDE2, SW V1.05
Appendix B Accessories|VFD-M-D Series
st
Environment, restricted distribution)
B-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents