The Multi-Function Input Terminals (refer to Pr.5-00 to 5-10) are used to select one of the AC
motor drive Multi-step speeds. The speeds (frequencies) are determined by Pr.5-17 to 5-32 as
shown above.
When using with door control system (Pr.0-09=02/03/04), it will run the door open/close curve
by the output of position sensor to change speed.
5 - 33

Multi-function Input Terminal Status (N.O/N.C)

Settings
It is used to set multi-function input terminals FWD, REV and output status of Pr.5-00 to Pr.5-
10 to be normal open (N.O.) or normal closed (N.C.).
Setting methods:
It needs to conver 13-bit binary value to decimal value before entering this parameter.
For example: Suppose that the initial status of REV, MI2, MI4, MI5, COM1, COM2 and COM4
is N.C. The initial status of FWD, MI1, MI3, A, B and COM3 is N.O. At this moment, you need
to input 5738 into Pr. 5-33 as shown in the following.
The setting value
12
= bit14x2 +
bit13x2 +....+bit2x2 +bit1x2 +bit0x2
12
10
= 1x2 +
1x2 +1x2 +1x2 +1x2 +1x2 +1x2
=4096+1024+512+64+32+8+2
Setting 5-33
Revision Jan. 2007, MDE2, SW V1.05
0 to 8191
Weights
Bit
1
0
1
1
0
11
2
1
9
6
5
3
=5738
0
1
1
0
1
0
1
0
NOTE:
0
14
13
2 =16384 2 =8192
1
9
8
2 =512
2 =256
4
3
2 =16
2 =8
Chapter 5 Parameters|VFD-M-D Series
Factory Setting: 0
0=N.O
1=N.C
FWD
=N.O
REV
=N.C
MI1
=N.O
MI2
=N.C
MI3
=N.O
MI4
=N.C
MI5
=N.C
A
=N.O
B
=N.O
COM1 =N.C
COM2 =N.C
COM3 =N.O
COM4 =N.C
12
11
10
2 =4096
2 =2048
2 =1024
7
6
5
2 =128
2 =64
2 =32
2
1
0
2 =4
2 =2
2 =1
Unit: 1
5-59