Daikin EBLQ05+07CAV3 Installer's Reference Manual page 58

Altherma low temperature monobloc
Table of Contents

Advertisement

8 Configuration
#
Code
[7.7.2.1]
[0-00]
<< continuation
[0-01]
▪ [0-03]:
temperature. –40°C~+5°C (default: –
[0-02]
10°C)
[0-03]
▪ [0-02]:
temperature.
15°C)
▪ [0-01]:
temperature
temperature equals or drops below
the
[9‑05]~[9‑06] (default: 45°C).
Note: This value should be higher
than [0-00] as for low outdoor
temperatures
required.
▪ [0-00]:
temperature
temperature equals or rises above
the
[9‑05]~min(45,
35°C).
Note: This value should be lower
than [0-01] as for high outdoor
temperatures less warm water is
required.
#
Code
[7.7.2.2]
[0-04]
Set weather-dependent cooling:
T t
[0-05]
[0-06]
[0-05]
[0-07]
[0-04]
▪ T
(additional)
▪ T
Installer reference guide
58
Description
Low
outdoor
ambient
High
outdoor
ambient
10°C~25°C
(default:
Desired
leaving
water
when
the
outdoor
low
ambient
temperature.
warmer
water
Desired
leaving
water
when
the
outdoor
high
ambient
temperature.
[9‑06])°C
(default:
Description
[0-07]
[0-06]
: Target leaving water temperature
t
: Outdoor temperature
a
continued >>
#
Code
[7.7.2.2]
[0-04]
[0-05]
[0-06]
[0-07]
is
Leaving water temperature: Delta T source
Temperature difference for entering and leaving water. The unit is
designed to support under floor loops operation. The recommended
leaving water temperature (set by the user interface) for under floor
loops is 35°C. In such case, the unit will be controlled to realize a
temperature difference of 5°C which means that the entering water
to the unit is around 30°C. Depending on the installed application
(radiators, heat pump convector, under floor loops) or situation, it
T a
can be possible to change the difference between entering and
leaving water temperature. Note that the pump will regulate its flow
to keep the Δt.
#
Code
[A.3.1.3.1]
[9-09]
[A.3.1.3.2]
[9-0A]
Leaving water temperature: Modulation
Only applicable in case of room thermostat control. When using the
room thermostat functionality, the customer needs to set the desired
room temperature. The unit will supply hot water to the heat emitters
and the room will be heated. Additionally, also the desired leaving
EBLQ05+07CAV3 + EDLQ05+07CAV3 + EKCB07CAV3 +
EK2CB07CAV3 + EKMBUHCA3V3 + EKMBUHCA9W1
Description
<< continuation
▪ [0-07]:
Low
outdoor
temperature.
10°C~25°C
20°C)
▪ [0-06]:
High
outdoor
temperature.
25°C~43°C
35°C)
▪ [0-05]:
Desired
leaving
temperature
when
the
temperature equals or drops below
the low ambient temperature.
Between minimum and maximum
leaving
water
temperature
[9‑07]~[9‑08] (default: 12°C).
Note: This value should be higher
than [0‑04] as for low outdoor
temperatures
less
cold
suffices.
▪ [0-04]:
Desired
leaving
temperature
when
the
temperature equals or rises above
the high ambient temperature.
Between minimum and maximum
leaving
water
temperature
[9‑07]~[9‑08] (default: 8°C).
Note: This value should be lower
than [0‑05] as for high outdoor
temperatures
colder
water
required.
Description
Heating: required temperature
difference between entering and
leaving water.
In case a minimum temperature
difference is required for the good
operation of the heat emitters in heating
mode.
Range: 3°C~10°C (in steps of 1°C;
default value: 5°C).
Cooling: required temperature
difference between entering and
leaving water.
In case a minimum temperature
difference is required for the good
operation of the heat emitters in cooling
mode.
Range: 3°C~10°C (in steps of 1°C;
default value: 5°C).
Daikin Altherma low temperature monobloc
4P405544-1 – 2015.03
ambient
(default:
ambient
(default:
water
outdoor
water
water
outdoor
is