8 Configuration
#
Code
[A.2.1.9]
[F-0D]
When the space heating/cooling control
is OFF by the user interface, the pump is
always OFF. When the space heating/
cooling control is On, you can select the
desired pump operation mode (only
applicable during space heating/cooling)
Pump operation mode:
▪ 0 (Continuous): Continuous pump
operation, regardless of thermo ON or
OFF condition. Remark: continuous
pump operation requires more energy
than
operation.
b
b
▪ a: Space heating/cooling control
▪ b: OFF
▪ c: On
▪ d: Pump operation
#
Code
[A.2.1.9]
[F-0D]
<< continuation
▪ 1 (Sample): The pump is ON. When
there is heating or cooling demand as
the
reached the desired temperature yet.
When thermo OFF condition occurs,
the pump runs every 5  minutes to
check the water temperature and
demand
necessary. Remark: Sample is NOT
available in extended room thermostat
control or room thermostat control.
a
b
d
g
b
▪ a: Space heating/cooling control
▪ b: OFF
▪ c: On
▪ d: LWT temperature
▪ e: Actual
▪ f: Desired
▪ g: Pump operation
Installer reference guide
52
Description
sample
or
request
pump
a
c
c
d
(user interface)
continued >>
Description
leaving
temperature
has
heating
or
cooling
c
e
f
c
(user interface)
continued >>
#
Code
[A.2.1.9]
[F-0D]
#
Code
[A.2.1.B]
N/A
not
if
[A.2.1.C]
[E-0D]
8.2.3
Quick wizard: Options
External domestic hot water pump
This chapter only applies to systems with a domestic hot water tank
installed. A domestic hot water tank is available as an option.
Following settings must be made accordingly.
EBLQ05+07CAV3 + EDLQ05+07CAV3 + EKCB07CAV3 +
EK2CB07CAV3 + EKMBUHCA3V3 + EKMBUHCA9W1
Description
<< continuation
▪ 2 (Request)(default): Pump operation
based on request. Example: Using a
room thermostat creates thermo ON/
OFF condition. When there is no such
demand, the pump is OFF. Remark:
Request is NOT available in leaving
water temperature control.
a
b
c
d
c
b
e
b
c
▪ a: Space heating/cooling control
(user interface)
▪ b: OFF
▪ c: On
▪ d: Heating demand (by ext RT or
RT)
▪ e: Pump operation
Description
Only if there are 2 user interfaces (1
installed in the room, 1 installed at the
indoor unit):
a
▪ a: At unit
▪ b: In room as room thermostat
User interface location:
▪ At unit: the other user interface is
automatically set to In room and if RT
control is selected act as room
thermostat.
▪ In room (default): the other user
interface is automatically set to At unit
and if RT control is selected to act as
room thermostat.
Glycol present:
▪ 0 (No) (default): No glycol was added
to the water circuit.
▪ 1 (Yes): Glycol was added to the water
circuit to protect it against freezing.
Daikin Altherma low temperature monobloc
4P405544-1 – 2015.03