Daikin EBLQ05+07CAV3 Installer's Reference Manual page 111

Altherma low temperature monobloc
Table of Contents

Advertisement

14.9
ESP curve
14.9.1
ESP curve: Outdoor unit
Note: A flow error will occur when the minimum water flow rate is not
reached.
A (kPa)
80
70
60
50
40
30
C
20
10
0
0
5
10
15
20
A (kPa)
80
70
60
50
40
C
30
20
10
0
0
5
10
15
20
A
External static pressure
B
Water flow rate
C
Operation range
Notes:
▪ The operation area is extended to lower flow rates only in case the
unit operates with heat pump only, and the temperature of the flow
medium is sufficiently high. (This does not apply to start‑up
operation, defrost operation, and backup heater operation in case
a backup heater is installed.)
▪ About the dashed lines: the higher operation range limit is only
valid if the flow medium is water. If glycol is added to the system,
the limit is lower.
▪ Selecting a flow outside the operating area can damage the unit or
cause the unit to malfunction.
EBLQ05+07CAV3 + EDLQ05+07CAV3 + EKCB07CAV3 +
EK2CB07CAV3 + EKMBUHCA3V3 + EKMBUHCA9W1
Daikin Altherma low temperature monobloc
4P405544-1 – 2015.03
E(D/B)LQ05CAV3
25
30
35
40
B (l/min)
E(D/B)LQ07CAV3
25
30
35
40
B (l/min)
14 Technical data
Installer reference guide